Rexroth EcoDrive 03 DKC**.3-016 Instructions for Use 5-13
DOK-ECODR3-DKC16*UL***-IB01-EN-P
Expansion interface
AP5376F1.FH7
device external device internal
X10
1
2
3
4
5
6
IAN+
0V
IAN-
IAN+
IAN-
0V
IAN+
IAN-
Fig. 5-29: Expansion interface
drive or
E/A-
module
drive or
E/A-
module
drive
120 R
120 R
IAN+
IAN-
EcoX bus
3,5V
2,5V
1,5V
voltage
time
dominant
recessive
IAN+
IAN-
recessive
SV5179F1.FH7
Fig. 5-30: EcoX interface
max. bus length l: 20 m
bus terminating resistors on both ends of the
bus cable
2 x 120 R / 250 mW
XE1, XE2 Protective Conductor Connections for Motor and Mains
DANGER
Lethal electric shock caused by live parts with
more than 50 V!
Connect the protective conductor connections of the
drive controller to the protective conductor system of
the control cabinet.
Cross section of protective conductor: > 10 mm²
(Reason: high leakage currents (EN 50178/1998,
section: 5.3.2.1)
Check the continuity of the protective conductors
from the mains connection to the connected motors.
Technical description of connector
Type No. of pins Design
screw-in connection 2 x 1 screw-in connection for
ring terminals M5
Fig. 5-31: Design
Connection
Expansion interface:
EcoX-Bus:
Bus cable:
Design: