Rexroth EcoDrive 03 DKC**.3-016 Instructions for Use 5-11
DOK-ECODR3-DKC16*UL***-IB01-EN-P
Ap5385f1.fh7
X1
X6
24V
to the central
ground
Fig. 5-24: Shared voltage source for brakes and control voltage supply
Note: Looping through the voltages to other drive controllers is
impossible. Other drive controllers have to be connected in
radial arrangement around the voltage source.
max. voltage at X6.4 against X6.5: DC 36 V
current consumption at X6.3 and needed
supply voltage:
see "Technical data" brake in
the motor manual
wire cross section:
min. 1 mm²
voltage resistance of single wire to ground
> 750 V
(e.g.: litz wires - H07)
wire routing
parallel if possible
(twisted)
max. inductance between 24 V source
and X6
100 µH
(equals about 2 x 75 m)
Motor holding brake
The controller controls the holding brake.
Supply voltage, current consumption, linking, separating time, holding
torque, etc. see motor manual.
Voltage connection for brakes
on DKC:
wire
voltage connection for brake:
Controlling the motor holding
brake:
Technical data
Motor holding brake: