Series 71 – Modulating Controller - Electric Actuator
Installation, Operation and Maintenance Manual
Output Signal Type - Configurable
Output signals report the position of the valve under control based on the
magnitude of the signal The minimum value corresponds to the closed
position and the maximum value to the open position Only one output
signal can be active at a time
Output Setting Description
-mA (default) Analog Current Range
Minimum mA
Maximum mA
-V Analog Voltage Range
Minimum V
Maximum V
-V Analog Voltage Range
Minimum V
Maximum V
Figure  S Servo Input Settings
Failure Position Last
The Failure Position determines how the S Servo positions the valve
upon loss of input signal Loss of input signal occurs when the input signal
received is outside the valid range of the selected Input Signal Type eg
an input signal of less than mA for the -mA input The S Servo will
position the valve at the last valid commanded position before loss of signal
Dead Band Control
Dead Band Control determines the acceptable offset between the position
command provided by the input command and the current position
of the actuator determined from the feedback signal provided by the
potentiometer This value is a percentage of the full input range and creates
an inactive area centered around the desired set point For example for
a -V input command the  Dead Band setting allows the actuator
position to be offset from the desired set point by up to V in either
direction creating a dead band with a span of V
Heater Setpoint
The S Servo maintains surveillance of the internal temperature of the
actuator If the internal temperature rises above F (C) the S Servo
will automatically turn off the W anti-condensation heater

Operating Modes
 Remote Operation
By default the operating mode of the S Servo is remote mode where
the valve is positioned based on input signals Exiting another mode of
operation generally results in the S Servo returning to remote mode