T
Taylor HansenAug 3, 2025
What to do if Bray Controller actuator does not fully close valve (or open valve)?
- RRobert JacobsAug 3, 2025
If the Bray Controller actuator doesn't fully close or open the valve, several factors could be at play. First, check if the limit switches are depressed and readjust the travel limit switches. Second, examine whether a mechanical travel stop is impeding the actuator and adjust the mechanical travel stops. Also, the valve torque requirement might be higher than the actuator output; in this case, manually override it out of the seat, try angle seating, or consider a larger actuator. Fourth, optional torque switches might be activating because the valve torque exceeds the actuator torque rating, so you may need to consult the factory. Finally, ensure that the voltage power supply is sufficient and check the power source.