EasyManuals Logo

Bryant 926SB User Manual

Bryant 926SB
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
926SB: Installation, Start-up, Operating, Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
Maximum Allowable Exposed Vent Length in Unconditioned Space (Metric)
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length calculated from Table 15.
† Insulation thickness based on R value of 3.5 per in.
Installing the Vent Pipe Adapter and Combustion Air
Pipe Adapter
NOTE: The rubber coupling that attaches to the vent pipe adapter must
be used. The adapter seals the vent pipe to the casing and reduces the
strain on the vent elbow attached to the inducer.
1. Apply the gaskets to the vent pipe and combustion air pipe
adapters. If supplied, remove and discard round center “slug” from
interior of gasket. See Fig. 58.
A13074
Fig. 58 – Vent Coupling and Adapter with Gaskets
NOTE: The vent pipe adapter can be distinguished from the inlet pipe
adapter by the absence of an internal pipe-stopping ring. The vent pipe
can pass through the vent pipe adapter; it cannot pass through the inlet
pipe adapter.
2. Align the screw holes in the plastic vent pipe adapter with the
dimples in the casing.
Winter
Design
Temp
°C
Unit Size
40,000* BTUH
60,000 BTUH
Uninsulated
3/8-in.
Insulation
1/2-in.
Insulation
Uninsulated 3/8-in. Insulation 1/2-in. Insulation
Pipe Dia.
mm
38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64 76 38 51 64 76
-7 6.1 6.1 6.1 6.1 15.2 13.7 6.1 18.3 15.2 6.1 9.1 9.1 7.6 6.1 22.9 19.8 18.3 6.1 25.9 22.9 19.8
-18 3.0 1.5 1.5 6.1 7.6 6.1 6.1 9.1 7.6
4.6 4.6 3.0 3.0 6.1 12.2 9.1 7.6 6.1 13.7 12.2 9.1
-29 1.5 6.1 4.6 3.0 6.1 6.1 4.6 3.0 1.5 6.1 7.6 6.1 4.6 6.1 9.1 7.6 6.1
-40
4.6 3.0 1.5 4.6 4.6 3.0 1.5 6.1 4.6 4.6 3.0 6.1 6.1 4.6 3.0
Winter
Design
Temp
°C
Unit Size
80,000 BTUH
Uninsulated 3/8-in. Insulation 1/2-in. Insulation
Pipe Dia.
mm
38 51 64 76 102 38 51 64 76 102 38 51 64 76 102
-7 4.6 12.2 12.2 10.7 9.1 4.6 15.2 27.4 22.9 19.8 4.6 15.2 21.3 21.3 21.3
-18 4.6 6.1 4.6 3.0 1.5 4.6 15.2 13.7 10.7 9.1 4.6 15.2 15.2 12.2 10.7
-29 4.6 3.0 1.5
4.6 10.7 9.1 6.1 4.6 4.6 12.2 9.1 7.6 4.6
-40 3.0 1.5 4.6 7.6 6.1 4.6 1.5 4.6 9.1 7.6 6.1 3.0
Winter
Design
Temp
°C
Unit Size
100,000 BTUH
Uninsulated 3/8-in. Insulation 1/2-in. Insulation
Pipe Dia.
mm
51 64 76 102 51 64 76 102 51 64 76 102
-7 6.1 15.2 12.2 10.7 6.1 24.4 28.9 24.4 6.1 24.4 32.0 27.4
-18 6.1 6.1 4.6 3.0 6.1 16.8 13.7 10.7 6.1 19.8 16.7 13.7
-29 4.6 3.0 1.5
6.1 10.7 9.1 6.1 6.1 13.7 10.7 7.6
-40 3.0 1.5
6.1 7.6 6.1 3.0 6.1 9.1 7.6 4.6
Winter
Design
Temp
°C
Unit Size
120,000 BTUH
140,000 BTUH
Uninsulated 3/8-in. Insulation 1/2-in. Insulation Uninsulated 3/8-in. Insulation 1/2-in. Insulation
Pipe Dia.
mm
64 76 102 64 76 102 64 76 102 64 76 102 64 76 102 64 76 102
-7 3.0 15.2 12.2 3.0 22.9 28.9 3.0 22.9 32.0 1.5 16.7 15.2 1.5 19.8 32.0 1.5 19.8 38.1
-18 3.0 6.1 4.6 3.0 16.8 13.7 3.0 19.8 15.2
1.5 7.6 4.6 1.5 19.8 15.2 1.5 19.8 18.3
-29 3.0 3.0
3.0 10.7 7.6 3.0 13.7 9.1 1.5 3.0 1.5 1.5 13.7 9.1 1.5 15.2 12.2
-40 3.0 1.5
3.0 7.6 4.6 3.0 9.1 6.1 1.5 1.5 1.5 9.1 6.1 1.5 35 7.6
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
DO NOT use cement to join polypropylene venting systems. Follow
the polypropylene venting system manufacturer’s instructions for
installing polypropylene venting systems.
Attach gaskets to vent pipe and
combustion air adapters.
Vent Coupling and Adapter

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bryant 926SB and is the answer not in the manual?

Bryant 926SB Specifications

General IconGeneral
BrandBryant
Model926SB
CategoryFurnace
LanguageEnglish

Related product manuals