EasyManua.ls Logo

Buderus SB615 - 5.5-5.6 Component Installation

Buderus SB615
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
Installation of the boiler
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
15
5.5 Installing the minimum pressure
switch and minimum pressure
limiter
B Connect the minimum pressure monitor or minimum
pressure limiter (with R½ to R¼ connection piece
adapter) to the MDW/MDB connection on the boiler
(Æ Fig 5).
Fig. 5 Logano plus SB615 Gas boiler connections
5.6 Low water indicator (accesory),
fitting (400 – 600 kW)
B Seal the flow pipe for the low water indicator into the
2" LWI connection on the boiler (Æ Fig. 5).
B Fit the low water indicator onto the low water indicator
tube.
B If the LWI connection is not being used for the
installation of a low water indicator, remove the plastic
plug and close off the LWI connection with a blanking
plug.
Note that a minimum pressure monitor must
be connected for 145 kW to 240 kW!
For 310 kW (145 kW and higher in Poland)
a minimum pressure limiter (MDB) must be
installed. This requires an R½ to connection
piece adapter .
For Germany
B For boilers > 300 kW, install a low water
indicator or minimum pressure limiter as
required by DIN-EN 12 828.
B For installation and operation, refer to the
technical documents provided by the
manufacturer.
For Poland
B For boilers > 100 kW, equip the boiler
with a low water indicator as required by
PN-91/B-2414 (p2.5).

Table of Contents

Related product manuals