8
Inspection/maintenance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
45
Condition-based maintenance Page (individual steps) Comments
1. Shut down the heating system. (Disconnect your heating
system from the main electrical supply, isolate main fuel
shut-off, disconnect flue pipe from burner.)
page 38
2. Cleaning hot gas flues (heating surfaces). page 40
3. Clean the combustion chamber.
Clean the condensate outlet.
Cleaning the flue collector.
page 40
4. Check and, if required, replace gaskets/packing cord on
the burner door.
5. Start up the heating system. page 34
6. Final maintenance check; take measurements and docu-
ment figures and test results.
Æ burner documentation
7. Check the function and operational safety (safety equip-
ment).
Confirm professional maintenance with signature, date and company stamp