EasyManua.ls Logo

Buderus SB615 - Page 7

Buderus SB615
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
Information about the appliance
Logano plus SB615 Gas - We reserve the right to make any changes due to technical modifications.
7
Specifications for Logano plus SB615 Gas
Boiler size Unit 145 185 230
1)
/240 310 400 510 640
Length
L mm 1816 1816 1845 1845 1845 1980 1980
L
K
mm 1746 1746 1774 1774 1774 1912 1912
Burner length
L
BR
- Logatop VM mm 376 376 376 376
L
BR
- WG mm 500 500 500 500 577 868 868
L
BR
- BS/M mm 280 301
L
BR
- RS/M mm 580 580 580 580 840
L
BR
- RS/M BLU mm 840
Width
B mm 900 900 970 970 970 1100 1100
Height
H mm 1606 1606 1638 1638 1842 2000 2000
H
K
mm 1376 1376 1408 1408 1612 1770 1770
Width/height/ for transport mm 720/1340 720/1340 790/1370 790/1370 790/1570 920/1730 920/1730
Length mm 1735 1735 1760 1760 1760 1895 1895
Base frame B
GR
mm 720 720 790 790 790 920 920
Clearance A mm 285 285 285 285 285 367 367
Flue outlet
ØD
AA
inside DN 183 183 203 203 253 303 303
H
AA
mm 300 300 305 305 333 370 370
Combustion chamber
Length mm 1460 1460 1460 1460 1460 1594 1594
Ø mm 453 453 453 453 550 650 650
Burner door
Depth mm 185 185 185 185 185 185 185
H
B
mm 985 985 1017 1017 1135 1275 1275
Boiler flow
2)
ØVK DN656580 80100100100
H
VK
mm 1239 1239 1260 1260 1442 1613 1613
Boiler return 1
2)
Ø RK1 DN 65 65 80 80 100 100 100
H
RK1
mm 142 142 142 142 150 150 150
A
1
mm 275 275 300 300 290 284 284
Boiler return 2
2)
ØRK2 DN R 1½ R 1½ R 1½ 65 65 80 80
H
RK2
mm 495 495 512 512 597 685 685
A
2
mm 295 295 310 310 315 360 360
Flow, safety line
3)
Ø VSL DN R 1¼ R 1¼ 32 32 50 50 50
H
VSL
mm 1180 1180 1213 1213 1327 1549 1549
A
3
mm 160 160 170 170 210 195 195
Condensate outlet
H
AKO
mm 164 164 164 164 164 160 160
A
4
mm 100 100 120 120 140 155 155
Drain H
EL
mm 85 85 82 82 90 138 138
Logatop gas connection VM DN 2
Combustion heat output
of kW 54.3 69.3 89.8 116.0 149.5 191.6 239.9
up to kW 135.8 173.2 224.4 289.9 373.8 478.9 599.8
Logatop VM
Partial load
35% kW
47.5 60.6 75.3 101.5 – – –
Full load
kW
135.8 173.2 215 289.9
CO
2
content % 10
Weight
net kg 613 620 685 705 953 1058 1079
With burner kg 648/643
1)
655/650
1)
720/715
1)
753/735
1)
1001 1156 1177
Water capacity l 560 555 675 645 680 865 845
Gas capacity l 327 333 347 376 541 735 750
Free draught Pa 50
1)
/boiler-dependent
4)
.
Hot gas resistance mbar 1.20 1.55 2.20 2.40 3.00 3.55 4.40
Permissible flow temperature
5)
°C 120
Permissible operating pressure bar 4 4 5 5 5.5 5.5 5.5
CE mark, boiler CE-0085 AT 0075
Tab. 1 Specification