12
7.4. Connecng the safety heat
exchanger
*
Such connecon must be
performed by a technician /
service shop authorized for such
operaons.
The heang boiler is equipped with
safetyheatexchanger(coolingcircuit).It
connects to the water system through a
thermostacvalve.Incaseofoverheang,
thethermostacvalvefeedsincoldwater
from the water mains which passes
throughtheheatexchangerandabsorbs
theheatintheboiler.
1. Water supply network (pressure 6-10 bar)
2. Drainage (sewerage)
3. Boiler WBS Acve
4. Safety heat exchanger inlet
5. BVTS valve sensor
6. Safety heat exchanger outlet
Diagram 6
The water is then discharged into the
sewage system. This arrangement
ensures safe evacuaon of the excess
heat without the need for addional
energy.Thisguaranteesthatthewaterin
the boiler will not exceed the maximum
safelevelof95°C.
The minimum operang pressure of the
coolingwaterinthesafetyheatexchanger
mustbewithintherange2-10bar.
Aowrateofatleast12l/minisrequired.
Connect the safety heat exchanger
accordingtothehydraulicdiagramusing
thermostac valve. Install a lter on the
inletbeforethethermostacvalve.
7.5. Connecondiagrams
*
Such connecons must be
performed by a technician /
serviceshopauthorizedforsuch
operaons.