TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
*
Cauon! These parameters can
be set only by an authorized
Professional Installer.
BOILER SHOULD TEMP - This parameter
species the maximum working
temperature.
EXHAUST MAX TEMP - This parameter
species the maximum temperature of
exhaustgasesinoperangmode(Work).
Thecontrollermonitorsthetemperature
and keeps the specied value via fan
performancemanagement.
EXHAUST MIN TEMP - This parameter
sets the temperature of exhaust gas at
whichthecontrollershisfromringup
modetooperaonmode.
*
Important:Inorder toshifrom
ringupmodetooperaonmode
itisnecessarytobemetthepreset
parameter values EXHAUST MIN
TEMP and 02 GO TO REGULATION
02 MAX TEMPERATURE-Thisparameter
species the percentage of oxygen in
the exhaust gases to be monitored and
sustained by controller in operaon
mode.
02 MIN TEMPERATURE-Thisparameter
sets the percentage of oxygen to be
monitoredandsustainedbycontrollerin
minimumpowerboileroperaonmode.
EXHAUST TEMP RISE -Thisparametersets
the temperature at which the controller
shisfromtheloadingtoring-upmode.
WAIT LAMBDA HEAT ON-Thisparameter
sets the calibraon me of the lambda
sensor.Theminimumvalueis2min.
O2 VALUE IN IGNITION-Thisparameter
species the percentage of oxygen
contentinexhaustgasatwhichcontroller
switches mode from Ignion“ to Burn
On“.
MAX IGNITION TIME - This parameter
species the maximum boiler me in
Ignion“ mode. If the boiler does not
shi to Work“ mode, there is either
a fuel problem or boiler gaskets issue -
pleasecontactYourinstaller.
02 GOTO REGULATION - This parameter
species the minimum percentage of
oxygen in the exhaust gas at which
controller shis from Burn On“ to
Work“mode.
EXH GOTO REGULATION-Thisparameter
sets the value of exhaust gases
temperature above which shis from
Burn On“to„Work“mode
MAX BURNON TIME - This parameter
species the maximum me in minutes
fortheboilertoshifromBurn On“to
Work“mode.