8

There is a small amount of noise emitted from the Mini ES. Although there is
only a small amount of noise emitted, 40 decibels, place in a location that will
not disturb the homeowner.
The location temperature must never fall below 0 degrees centigrade, or
exceed 40 degrees centigrade.
2.2.2 Room sizes
The room has to be larger than 8.00 m³
If the room size is 8-25m³, it needs ventilation which is at 12 m³/h of air change
rate.
If the room size is over 25m³, it doesn’t need separate ventilation equipment.
The minimum base surface area is 2.00
- Min. height is 2.00 m
- Min. depth is 2.00 m
2.2.3 Ceiling, ground and wall requirements

The total weight of the device that the ground could support is 96kg (3kWh
system). The proximity to the grid consumption meter shouldn’t be too far to
install to allow CT cable connection without extending the CT (10m).

2.2.4 Temperature and humidity
 
Max. humidity is 95%.
2.2.5 Access rights
Children must be accompanied with an adult if they are in the installation room.
Children must not operate the storage system.