EasyManua.ls Logo

Calorex Variheat AA600 - Page 29

Calorex Variheat AA600
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
29
1002595 ISSUE 5 M172 VARIHEAT
PLC ETHERNET SETTINGS
Press e button on e right.
Arrow icon
Return to
User Settings
Home icon
Return to
Home screen
This screen contains settings related to BMS connectivity using BACnet/IP
rough e Eernet port on e PLC. The factory default settings are shown. If
connecting using Modbus/RTU or BACnet MS/TP, see e BMS Settings screen
on page 31.
Enable DHCP. This button toggles between DHCP enabled or disabled.
IP Address, Subnet Mask, Default Gateway, Primary and Secondary DNS – all
fields can be set from 0 to 255.
HTTP Port. Can be set from 0 to 65535. 0 corresponds to default port 80.
TCP/IP Port Can be set from 0 to 65535. Default is 502.
Aer changing any of e above settings, restart e PLC/Variheat, by
cycling e power supply on/off, to save and apply e new settings.
For Modbus Variable list and BACnet Object list please consult e Danerm
Group.

Related product manuals