Functions mapping
F 1 Total stop function (1-2)
F 2 Function associated with CX input
F 3 Function associated with CY input
F 5 Safety test function
F 6 Hold-to-run function
F 9 Obstruction detection function with motor idle
F 10 Indicator light function
F 11 Exclude encoder
F 14 Sensor type selection function
F 15 Luminous cord intermittence function
F 18 Additional light function
F 19 Automatic closing time
F 21 Pre-flashing time
F 22 Working time
F 25 Courtesy light time
F 28 Opening speed adjustment
F 29 Closing speed adjustment
F 30 Opening slow-down speed adjustment
F 31 Closing slow-down speed adjustment
F 33 Calibration speed adjustment
F 34 Sensitivity during movement
F 35 Sensitivity during slow-down
F 37 Adjustment of opening slow-down starting point
F 38 Adjustment of closing slow-down starting point
F 49 Activation of serial connection
F 50 Save data to the memory roll
F 51 Read data on the memory roll
F 52 Parameter transfer from Master to Slave
F 60 Sleep mode
F 61 Pre-flashing function
U 1 Type of command to associate with user using radio control
U 2 Delete a single user
U 3 Delete all users
A 1 Set boom type
A 2 Motor test
A 3 Travel calibration
A 4 Parameter reset
A 5 Count number of manoeuvres
H 1 Software version
Functions menu
F1 Total stop [1-2] 0 = Deactivated (default) / 1 = Activated
N.C. Input – Stop boom while excluding automatic closing; to resume movement, use the command device. The safety device should be
inserted in [1-2].
F2 Input [2-CX] 0 = Deactivated (default) / 1 = C1 / 4 = C4 / 5 = C5 / 9 = C9
NC Input – Possible associations: C1 = reopening during closing by photocells, C4 = obstacle stand-by, C5 = immediate closure, C9 = im-
mediate closure with obstacle stand-by during closing.
F3 Input [2-CY] 0 = Deactivated (default) / 1 = C1 / 4 = C4 / 5 = C5 / 9 = C9
NC Input – Possible associations: C1 = reopening during closing by photocells, C4 = obstacle stand-by, C5 = immediate closure, C9 = im-
mediate closure with obstacle stand-by during closing.
IMPORTANT! Start programming these functions first: SET BOOM TYPE (A1), MOTOR TEST (A2), TOTAL STOP (F1) AND TRAVEL
CALIBRATION (A3).