45
Mask index Display description Description Default UOM Values
Ab02 (display only)
User setp.
User-defi ned set point for suction pressure control, proportional control
(line 1)
--- … …(**)
Actual.setpoint
Eff ective set point for suction pressure control, proportional control (with
compensation applied, line 1)
--- … …(**)
Neutral zone Neutral zone for suction pressure control (line 1) --- … …(**)
Incr.diff .
Increase diff erential for suction pressure control, neutral zone control (line
1)
--- … …(**)
Decr.diff .
Decrease diff erential for suction pressure control, neutral zone control
(line 1)
--- … …(**)
Ab03 (display only)
User setp.
User-defi ned set point for suction pressure control, proportional control
(line 2)
--- … …(**)
Actual.setp.
Eff ective set point for suction pressure control, proportional control (with
compensation applied, line 2)
--- … …(**)
Diff . Suction pressure control diff erential, proportional control (line 2) --- … …(**)
Ab04 (display only)
User setp.
User-defi ned set point for suction pressure control, proportional control
(line 2)
--- … …(**)
Actual.setp.
Eff ective set point for suction pressure control, proportional control (with
compensation applied, line 2)
--- … …(**)
Neutral zone Neutral zone for suction pressure control (line 2) --- … …(**)
Incr.diff .
Increase diff erential for suction pressure control, neutral zone control (line
2)
--- … …(**)
Decr.diff .
Decrease diff erential for suction pressure control, neutral zone control
(line 2)
--- … …(**)
Ab05 (display only)
User setp.
User-defi ned set point for condensing pressure control, proportional
control (line 1)
--- … …(**)
Actual.setp.
Eff ective set point for condensing pressure control, proportional control
(with compensation applied, line 1)
--- … …(**)
Diff . Condensing pressure control diff erential, proport.control (line 1) --- … …(**)
Ab06 (display only)
User setp.
User-defi ned set point for condensing pressure control, proportional
control (line 1)
--- … …(**)
Actual.setp.
Eff ective set point for condensing pressure control, proportional control
(with compensation applied, line 1)
--- … …(**)
Neutral zone Neutral zone for condensing pressure control (line 1) --- … …(**)
Incr.diff .
Increase diff erential for the condensing pressure control, neutral zone
control (line 1)
--- … …(**)
Decr.diff .
Decrease diff erential for the condensing pressure control, neutral zone
control (line 1)
--- … …(**)
Ab07 (display only)
User setp.
User-defi ned set point for condensing pressure control, proportional
control (line 2)
--- … …(**)
Actual.setp.
Eff
ective set point for condensing pressure control, proportional control
(with compensation applied, line 2)
--- … …(**)
Diff .
Condensing pressure control diff erential, proportional control
(line 2)
--- … …(**)