50
Mask index Display Description Description Default UOM Values
Cab01
Regulation by Compressor control by temperature or pressure (line 1) PRESSURE --- PRESSURE TEMPERATURE
Regulation type Compressor control type (line 1)
Neutral zone ---
Proportional band
Neutral zone
Cab02
Minimum Compressor setpoint lower limit (line 1) …(**) … …(**)
Maximum Compressor setpoint higher limit (line 1) …(**) … …(**)
Cab03 Setpoint Compressor setpoint (line 1) …(**) … …(**)
Cab04/Cab6 (**)
Reg.type Type for proportional control (line 1)
PROPORT. --- PROPORTIONAL PROP.+INT.
Integral time Integral time for proportional control (line 1) 300 s 0…999
Cab05/Cab7 (**) Diff erential Diff erential for proportional control (line 1) …(**) … …(**)
Cab08/Cab10 (**)
NZ diff . Neutral zone control diff erential (line 1) …(**) … …(**)
Activ.diff . Neutral zone control diff erential for device activation (line 1) …(**) … …(**)
Deact.diff . Neutral zone control diff erential for device deactivation (line 1) …(**) … …(**)
Cab09/Cab11 (**)
En.force off power Enable capacity immediate decreasing to 0 (line 1) NO --- NO / YES
Setp.for force off Threshold for capacity decreasing to 0 (line 1) …(**) … …(**)
Cab12
Power load to 100% min
time
Minimum time to increase capacity request to 100%, Neutral zone
control (suction line 1)
15 s 0…9999
Power load to 100% max
time
Maximum time to increase capacity request to 100%, Neutral zone
control (suction line 1)
90 s 0…9999
Cab13
Power unload to 0%
min time
Minimum time to decrease capacity request to 0%, Neutral zone control
(suction line 1)
30 s 0…9999
Power unload to 0%
max time
Maximum time to decrease capacity request to 0%, Neutral zone control
(suction line 1)
180 s 0…9999
Cac01
Working hours
Compressor 1
Compressor 1 operating hours (line 1)
--- h 0…999999
(Check in…) Compressor 1 remaining operating hours (line 1) … h 0…999999
Compressor 2 Compressor 2 operating hours (line 1) --- h 0…999999
(Check in…) Compressor 2 remaining operating hours (line 1) … h 0…999999
…… … ………
Cac11
Working hours
Compressor 11
Compressor 11 operating hours (line 1)
--- h 0…999999
(Check in…) Compressor 11 remaining operating hours (line 1) … h 0…999999
Compressor 12 Compressor 12 operating hours (line 1) --- h 0…999999
(Check in…) Compressor 12 remaining operating hours (line 1) … h 0…999999
Cac13
Compressor threshold
working hours
Compressor maintenance threshold hours (line 1)
88000 h 0…9999999
Cac14 Compressor hours reset Reset compressor operating hours (line 1) N --- NO / YES
Cad01
Enable suction setpoint
compensation
Enable setpoint compensation (suction line 1)
NO --- NO / YES
Enable compensation by
analog IN
Enable setpoint compensation by probe (suction line 1)
NO --- NO / YES
Cad02
Winter off set Off set applied for Winter period 0.0 … -999,9…999,9
Closing off set Off set applied for closing period 0.0 … -999,9…999,9
Cad03
Enable setpoint compen-
sation by scheduler
Enable scheduler setpoint compensation (suction line 1)
NO --- NO / YES