Model 99FRD, 100CRD & 102CRD oil burners — Instruction manual
Carlin part number MN99102 Rev. 08/20/08
– 6 –
Figure 1 99FRD, 100CRD and 102CRD Minimum combustion chamber dimensions (all dimensions in inches)
2. Prepare site • assemble burner • mount burner (continued)
Chamber configurations
A Chamberwithwater-backedoorandtargetwall,withrefractoryliningson
oorandtargetwall.
B Chamberwithwater-backedoor andtarget wall, withrefractorylining on
target wall only.
C Chamberwithwater-backedoorandtargetwall,withoutrefractorylinings.
D Refractorychamber,nowater-backedsurfaces(drybasedesign).
E Chamberwith refractory oorandwater-backed targetwall(without target
refractory lining).
F Chamberwithrefractoryoorandwater-backedtargetwall(with target refrac-
tory lining).
Notes for dimension table
1 Some tested appliancesoperate well withdimensions other thanshown
below.
2. Generally,applications should be acceptable with dimensions larger than
listed.
3. Horizontalcylinderchambersshouldhaveadiameteratleastaslargerasthe
minimum width listed. For steel cylinder chambers, increase this dimension
by from 1 to 4 inches.
4. Wingwallsarenotrecommended.Corbelscanbebenecialtoheatdistribution
in some applications.
5. DVistheminimumdiameterforverticalcylindricalchambers(refractoryor
refractory-lined chambers only).