39 62-11648
21. Emergency Bypass Mode
In the event of an alarm caused by a failure of the display module, the unit will
go into shutdown. To temporarily bypass this shutdown state, Emergency
Bypass Mode can be activated.
Once Emergency Bypass mode has been activated, the unit will operate
normally for 24 hours, a countdown timer will be shown on the display. This
24-hour window of operation will keep the load safe, and provide enough time
to contact the nearest Carrier Transicold Service Center for repair of the unit.
21.1 Enter Emergency Bypass Mode
1. When the unit is in a shutdown state due to the display module alarm,
press the MENU key until BYPASS MODE is displayed.
2. Press the BYPASS MODE soft key, the unit will resume operation until
Emergency Bypass mode is disabled, or after 24 hours of unit operation in
Emergency Bypass mode.
21.2 Exit Emergency Bypass Mode
1. Press the MENU key until the EXIT BYPASS soft key is displayed.
2. Press the EXIT BYPASS soft key, the unit will shut down. Once
Emergency Bypass mode is turned off, it cannot be restarted and the unit
will remain in shutdown until it is repaired.
START/STOP DIESEL
BOX TEMPERATURE
o
F SETPOINT
o
F
INSPECT
MODE
34.3
34
EXIT
BYPASS
MODE