Table 3 -- Alarm Configuration (ALARMDEF)
DESCRIPTION DISPLAY POINT RANGE
Alarm Configuration
Re-alarm Time xxx min RETIME 0-1440
Alarm Routing xxxxxxxx* ROUTING 0-11111111
*This is an 8-bit binary value, where each digit is 0 or 1.
DEFAULT
0
00000000
Table 4- Broadcast Configuration (BRODEF)
DISPLAY POINT RANGE DEFAULTDESCRIPTION
Real Time Clock
Time Broadcast Enable
Daylight Savings
Start Month
Start Day of Week
Start Week
Start Time
Start Advance
Stop Month
Stop Day of Week
Stop Week
Stop Time
Stop Back
Disable/Enable
XX
X
X
XX:XX
XXX min
XX
X
X
XX:XX
XXX rain
TIMEBCST
DAYSAV
DLSTRMON
DLSTRDOW
DLSTRWK
DLSTRTIM
DLSTRADV
DLSTPMON
DLSTPDOW
DLSTPWK
DLSTPTIM
DLSTPADV
0-1
1-12
1-7
1-5
0:00-24:00
0-360
1-12
1-7
1-5
0:00-24:00
0-360
Disable
4
7
1
2:00
6O
10
7
5
2:00
6O
Start Time -- Use this decision to enter the time of day at
which the real time clock will adjust the time for the start of
daylight saving time.
Start Time: Allowable Entries 0:00 to 24:00
Default Value 2:00
Start Advance -- Use this decision to enter the number of
minutes by which the real time clock will adjust the time for
the start of daylight saving time. An entry of 0 will disable this
feature.
Start Advance: Allowable Entries 0 to 360 min
Default Value 60 min
Stop Month -- Use this decision to enter the month in which
the real time clock will adjust the time for the end of daylight
saving time.
Stop Month: Allowable Entries 1 to 12
Default Value 10
Stop Day of Week -- Use this decision to enter the day of the
week on which the real time clock will adjust the time for the
end of &_ylight saving time.
Stop Day of
WEek: Allowable Entries 1 to 7
Default Value 7
Stop Week -- Use this decision to enter the week of the month
in which the real time clock will adjust the time for the end of
daylight saving time.
Stop Week: Allowable Entries 1 to 5
Default Value 5
Stop Time -- Use this decision to enter the time of day at
which the real time clock will adjust the time for the end of
daylight saving time.
Stop Time: Allowable Entries 0:00 to 24:00
Default Value 2:00
Stop Back -- Use this decision to enter the number of minutes
by which the real time clock will adjust the time for the end of
daylight saving time. An entry of 0 will disable this feature.
Stop Back: Allowable Entries 0 to 360 min
Default Value 60 min
Holiday (HOLDYxxS) Configuration Table -- The
Holiday Configuration Table is shown in Table 5. Up to 30
Holiday tables (HOLDY01S - HOLDY30S) may be config-
ured. An explanation of each configuration decision follows.
START MONTH -- Use this decision to indicate the month
of the year in which the holiday will begin.
Start Month: Allowable Entries 1 to 12
Default Value 1
START DAY -- Use this decision to indicate the day of the
month on which the holiday will begin.
Start Day: Allowable Entries 1 to 31
Default Value 1
DURATION -- Use this decision to indicate the number of
consecutive &Lys that the holiday will last. If you enter 0 in this
decision, the holiday schedule will be disabled.
Duration: Allowable Entries 0 = Disable or 1 to 365
Default Value 0
Remote Attach Configuration (REMOTE)
Table -- The Remote Attach Configuration Table is shown
in Table 6. An explanation of each configuration decision
follows.
REMOTE ATTACH ENABLE -- Use this decision to enable
the Remote Attach iimction. This function allows the System
Pilot to perform the following operations for a specified device
referred to as the "remote device." This limctionality occurs as
a background task to the System Pilot's normal functionality.
• write space temperature
• compute an operating mode
• monitor and modify set points
While the Remote Attach function is enabled, the System
Pilot can attach to (using the Progrmn screen Attach option)
and communicate with the remote device or any other device.
The Remote Attach will remain in effect until it is disabled.
Space temperature will be written to the remote device once
a minute or whenever the value changes by 0.3 E If a Remote
Attach is disabled, the System Pilot will auto the space temper-
ature variable in the remote device.
NOTE: If Remote Attach is being used with a VVT® zone
controllel: the System Pilot will write its space tempemtme to
the Zone Controllel: but will not perform the set point monitor-
ing/control or mode calculation. Set point monitoring/control
and mode calculation is performed for the Zone Controller
from the Zone Controller Default Screen.
Remote Attach: Allowable Entries Disable / Enable
Default Value Disable
13