Caution: Turn off the power switch before connecting or disconnecting the connector. Failure to do so could damage
the board.
NOTES:
1. Model 38VMA***HDS5-1 (208/230V-3Ph-60Hz):
L2 Error will be reported when it is higher than 500VDC, the over-voltage setting value for DC bus.
2. Model 38VMA***HDS6-1 (460V-3Ph-60Hz):
L2 Error will be reported when it is higher than 800VDC, the over-voltage setting value for DC bus.