If alternate vent position
is required, loosen clamp
on vent elbow inlet.
Remove the screw that secures the
condensate trap to the collector box
and remove trap.
Remove relief tube from
relief port on condensate
trap.
Remove front pressure
switch tube and discard.
A new tube is shipped in
the Loose Parts bag.
(_ emove relief tube
from port on collector --
box.
(1 AND 2 STAGE UNITS)
Remove middle and right
plug from collector box.
DO NOT DISCARD.
H
Unconverted Factory Trap Configuration
As Viewed in the Horizontal Left Orientation
NOTE: Remove knockout in
casing before re-installing the
condensate trap.
(_ Rotate elbow to
desired position
and torque clamp
on inlet 15 lb.-in.
Install two plugs previously
removed in open ports on
collector box.
Connect relief tube to port
on collector box.
(_ Slide relief tube instand-offs to adjust
length.
Connect the new pressure switch
tube from Loose Parts bag to port
on front pressure switch.
(_ ttach condensatetrap with screw to
collector box.
(_ Align trap over middleand right-hand port on
collector box.
\
(1 AND 2 STAGE UNITS)
Route pressure switch tube
underneath relief tube and
connect to port on
collector box.
Connect relief tube to relief
port on condensate trap.
Horizontal Left Trap Configuration
Fig. ll - Horizontal Left Configuration
(Appearance may vary)
Al1574