Carrier 59TN6A - Maximum Allowable Exposed Vent Lengths Insulation Table

Carrier 59TN6A
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Two Stage
Furnace High
Heat Input
Table 12 - Maximum Allowable Exposed Vent Lengths Insulation Table - Ft. / M
No Insulation 3/8-in. (9.5 mm)
Pipe
Length in
Ft. &M
Winter Design
Tempo F (oC)
20 (-10)
0 (-20)
-20 (-30)
-40 (-40)
Ft.
M
Ft.
M
40000*
Ft.
M
Ft.
M
PipeDiametePinches(mm)
1.5 2.0 2.5 3.0 4.0
(38) (51) (64) (76) (102)
40.0 35.0 35.0 N_ N_
12.2 10.7 10.7 N_ N_
19.0 14.0 12.0 N_ N_
5.8 4.3 3.7 N_ N_
9.0 3.0 1.0 N_ N_
2.7 0.9 0.3 N_ N_
3.0 0.0 0.0 N_ N_
0.9 0.0 0.0 N_ N_
PipeDiametePinches(mm)
1.5 2.0 2.5 3.0 4.0
(38) (51) (64) (76) (102)
50.0 104.0 94.0 N_ N_
15.2 31.7 28.7 N_ N_
50.0 61.0 54.0 N_ N_
15.2 18.6 16.5 N_ N_
50.0 41.0 35.0 N_ N_
15.2 12.5 10.7 N_ N_
39.0 29.0 23.0 N_ N_
11.9 8.8 7.0 N_ N_
1/2-in.(12.7mm)
PipeDiamete_inches(mm)
1.5 2.0 2.5 3.0 4.0
(38) (51) (64) (76) (102)
50.0 122.0 110.0 N_ N_
15.2 37.2 33.5 N_ N_
50.0 74.0 65.0 N_ N_
15.2 22.6 19.8 N_ N_
50.0 51.0 43.0 N_ N_
15.2 15.5 13.1 N_ N_
48.0 37.0 30.0 N_ N_
14.6 11.3 9.1 N_ N_
Ft. 30.0 51.0 51.0 45.0 N/A 30.0 135.0 138.0 120.0 N/A 30.0 135.0 162.0 141.0 N/A
20 (-10) M 9.1 15.5 15.5 13.7 N/A 9.1 41.1 42.1 36.6 N/A 9.1 41.1 49.4 43.0 N/A
Ft. 30.0 24.0 23.0 16.0 N/A 30.0 93.0 82.0 69.0 N/A 30.0 111.0 98.0 83.0 N/A
0 (-20) M 9.1 7.3 7.0 4.9 N/A 9.1 28.3 25.0 21.0 N/A 9.1 33.8 29.9 25.3 N/A
60000
Ft. 18.0 11.0 9.0 1.0 N/A 30.0 65.0 56.0 44.0 N/A 30.0 79.0 68.0 55.0 N/A
-20 (-30) M 5.5 3.4 2.7 0.3 N/A 9.1 19.8 17.1 13.4 N/A 9.1 24.1 20.7 16.8 N/A
Ft. 10.0 3.0 0.0 0.0 N/A 30.0 48.0 40.0 29.0 N/A 30.0 59.0 50.0 38.0 N/A
-40 (-40) M 3.0 0.9 0.0 0.0 N/A 9.1 14.6 12.2 8.8 N/A 9.1 18.0 15.2 11.6 N/A
Ft. 20.0 64.0 64.0 56.0 47.0 20.0 70.0 173.0 150.0 125.0 20.0 70.0 175.0 177.0 147.0
20 (-10) M 6.1 19.5 19.5 17.1 14.3 6.1 21.3 52.7 45.7 38.1 6.1 21.3 53.3 53.9 44.8
Ft. 20.0 32.0 30.0 22.0 11.0 20.0 70.0 104.0 87.0 67.0 20.0 70.0 124.0 104.0 82.0
0 (-20) M 6.1 9.8 9.1 6.7 3.4 6.1 21.3 31.7 26.5 20.4 6.1 21.3 37.8 31.7 25.0
80000
Ft. 20.0 17.0 14.0 6.0 0.0 20.0 70.0 71.0 57.0 40.0 20.0 70.0 86.0 71.0 52.0
-20 (-30) M 6.1 5.2 4.3 1.8 0.0 6.1 21.3 21.6 17.4 12.2 6.1 21.3 26.2 21.6 15.8
Ft. 15.0 7.0 5.0 0.0 0.0 20.0 61.0 52.0 40.0 24.0 20.0 70.0 64.0 50.0 33.0
-40 (-40) M 4.6 2.1 1.5 0.0 0.0 6.1 18.6 15.8 12.2 7.3 6.1 21.3 19.5 15.2 10.1
Ft. N/A 25.0 79.0 70.0 59.0 N/A 25.0 110.0 186.0 155.0 25.0 110.0 219.0 182.0
20 (-10) M N/A 7.6 24.1 21.3 18.0 N/A 7.6 33.5 56.7 47.2 7.6 33.5 66.8 55.5
Ft. N/A 25.0 40.0 31.0 19.0 N/A 25.0 110.0 109.0 86.0 25.0 110.0 131.0 104.0
0 (-20) M N/A 7.6 12.2 9.4 5.8 N/A 7.6 33.5 33.2 26.2 7.6 33.5 39.9 31.7
100000
Ft. N/A 23.0 21.0 13.0 0.0 N/A 25.0 91.0 74.0 54.0 25.0 110.0 90.0 68.0
-20 (-30) M N/A 7.0 6.4 4.0 0.0 N/A 7.6 27.7 22.6 16.5 7.6 33.5 27.4 20.7
Ft. N/A 13.0 10.0 1.0 0.0 N/A 25.0 68.0 53.0 35.0 25.0 83.0 66.0 46.0
-40 (-40) M N/A 4.0 3.0 0.3 0.0 N/A 7.6 20.7 16.2 10.7 7.6 25.3 20.1 14.0
Ft. N/A N/A 15.0 85.0 73.0 N/A N/A 15.0 100.0 190.0 N/A N/A 15.0 100.0 224.0
20 (-10) M N/A N/A 4.6 25.9 22.3 N/A N/A 4.6 30.5 57.9 N/A N/A 4.6 30.5 68.3
Ft. N/A N/A 15.0 41.0 29.0 N/A N/A 15.0 100.0 109.0 N/A N/A 15.0 100.0 131.0
0 (-20) M N/A N/A 4.6 12.5 8.8 N/A N/A 4.6 30.5 33.2 N/A N/A 4.6 30.5 39.9
120000
Ft. N/A N/A 15.0 20.0 7.0 N/A N/A 15.0 94.0 71.0 N/A N/A 15.0 114.0 88.0
-20 (-30) M N/A N/A 4.6 6.1 2.1 N/A N/A 4.6 28.7 21.6 N/A N/A 4.6 34.7 26.8
Ft. N/A N/A 15.0 7.0 0.0 N/A N/A 15.0 69.0 48.0 N/A N/A 15.0 85.0 62.0
-40 (-40) M N/A N/A 4.6 2.1 0.0 N/A N/A 4.6 21.0 14.6 N/A N/A 4.6 25.9 18.9
* Not all families have these models.
* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe
length calculated from Table 13 or 15.
1-Insulation thickness based on R value of 3.5 per in.