EasyManua.ls Logo

Carrier 62X Series - Cooling Status Screen; Reheat Status Screen; Dehumidification Status Screen

Carrier 62X Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Fig. 13 — Cooling Status Screen
The following information may be shown on the on Cooling 1 sta-
tus screen:
Clg Mode status indicates that the conditions are meet for
cooling.
The next parameter (shown as OAT above) indicates the
sensor to enable compressor #1 or circuit #1. The type of
sensor will change depending on control configuration.
Common configurations include:
- Outdoor air temperature (OAT)
- Entering coil air temperature (ECAT, with ECW)
- Outdoor air temperature vs supply air temperature (OAT
vs SAT)
- Outdoor air enthalpy (OAE)
Clg1 En SP is the setpoint to enable circuit #1. The set
point is adjustable on the Clg1 SP screen.
DXLAT (DX coil leaving air temperature) indicates the
sensor to modulate the compressor.
Clg1 MOD SP is the setpoint for modulating the compres-
sor. The setpoint is adjustable on the Clg1 SP screen.
The C1 Mod will display the percentage of analog output
(UO-07).
COS Status will display the status of the condensate over-
flow switch (COS) for the condensate drain pan
MIN OFF Timer reflects the 5 minutes the compressor
must be off before restarting.
MIN ON Timer reflects the 5 minutes the compressor must
be on before shutdown.
Heating to Cooling (Htg to Clg) Timer is a 10-minute tim-
er for the heating mode to cooling mode switchover.
RV Status will be displayed when the unit is a heat pump
(62H ASHP or 62W WSHP). The RV will display off
when the unit is in cooling mode or on when the unit is in
heat pump heating mode.
Indicator Lights:
- C1 EN will light when the enable conditions are met.
- Y1 will light when the UO-10 or compressor #1 is com-
manded on.
- CMP1 will light when the compressor #1 current sensor
shows amperage.
- HPS1 and LPS1 will be light in their normal state (N.C.).
When they go into alarm the light will turn off.
- FRZ1 will light when the freeze alarm is active for Com-
pressor #1.
Units with two refrigerant circuits (size 12+ tons) will also have a
Cooling 2 status screen. The above information will also be dis-
played for the second circuit (except for the COS).
The Reheat status screen shows the status and parameters for the
liquid subcooling reheat (Sub-Cooling, if equipped) and hot gas
reheat (ReHeat). See Fig. 14.
Fig. 14 — Reheat Status Screen
The following information may be shown on the on Reheat status
screen:
Sub-Cooling status will display the status of the liquid sub
cooling coil (if equipped).
Reheat Status will display the status of the hot gas reheat
coil.
Supply air temperature (SAT) indicates the sensor reading
for the SAT sensor.
SAT SP is the setpoint for modulating the reheat system.
The setpoint is adjustable on the Clg 1 SP screen.
RH Mod will display the percentage of analog output
(UO-04).
Indicator Lights:
- HGRH Manual Override will light when placed in man-
ual override
The Dehumidification 1 status screen shows the status and param-
eters for dehumidification mode for the first refrigerant circuit. For
units with two refrigerant circuits (12+ tons), A Dehum 2 status
screen will also be displayed with similar information. See
Fig. 15.
Fig. 15 — Dehumidification Status Screen
The following information may be shown on the on Dehum status
screen:
Outdoor air temperature (OAT)
Dehum1 will display the status of the dehum mode.
Lim SP is the low limit set point to enable the dehum mode
(typically based on OAT).

Table of Contents

Related product manuals