EasyManua.ls Logo

Carrier 62X Series - Heating Status Screen; Heat Pump 1 Status Screen; Set Points Screens

Carrier 62X Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
The next parameter (shown as OADP above) indicates the
sensor to enable the dehum mode. The type of sensor will
change depending on the unit configuration. Common con-
figurations include:
- Outdoor air dew point (OADP) vs supply air dew point
(SADP)
- Entering coil dew point (ECDP, with ECW) vs supply air
dew point (SADP)
- Supply air relative humidity (SARH)
EN SP is the setpoint to enable dehumidification based on
the configuration above.
The next parameter (shown as SADP) status indicates the
sensor to control cooling during dehum mode. The type of
sensor will change depending on the unit configuration.
Common configurations include:
- Supply air dew point (SADP)
- Supply air relative humidity (SARH)
MOD SP is the setpoint to modulate the cooling system
(lead compressor).
DH1 Mod will display the percentage of analog output
(UO-07) during dehumidification operation.
The Heating status screen shows the status and parameters the unit
heat source (if equipped). See Fig. 16.
Fig. 16 — Heating Status Screen
The following information may be shown on the Heating status
screen:
Htg Mode status indicates that the conditions are met for
heating.
The next parameter (shown as OAT above) indicates the
sensor to enable heating. The type of sensor will change
depending on the unit configuration. Common configura-
tions include:
- Outdoor air temperature (OAT)
- Entering coil air temperature (ECAT, with ECW)
Htg En SP is the setpoint to enable heating. The setpoint is
adjustable on the Htg SP screen.
SAT indicates the unit supply air temperature sensor,
which is used to modulate the heat source.
Htg SAT SP is the supply air temperature setpoint for mod-
ulating the heat soource. The setpoint is adjustable on the
Htg SP screen.
The Htg Mod will display the percentage of analog output
(UO-06).
Clg to Htg Timer is a 10-minute timer for the cooling
mode to heating mode switchover.
Indicator Lights:
- Htg EN will light when the heating enable condition is
met.
The Heat Pump 1 status screen shows the status and parameters
the heat pump units (62H and 62W only). Units with two refriger-
ant circuits (12+ tons) will also have a Heat Pump 2 status screen.
See Fig. 17.
Fig. 17 — Heat Pump 1 Status Screen
The following information may be shown on the Heat Pump 1 sta-
tus screen:
RV Status will display Off when the heat pump unit is in
cooling mode and ON when the unit is in heat pump heat-
ing mode.
Htg Mode status indicates that the conditions are met for
Heat pump heating.
OAT indicates the sensor to enable compressor #1 or cir-
cuit #1.
HP1 En SP is the setpoint to enable compressor #1 or cir-
cuit #1. The setpoint is adjustable on the HP1 SP screen.
SAT indicates the sensor to modulate the compressor.
MOD SP is the setpoint for modulating the compressor.
The setpoint is adjustable on the HP1 SP screen.
The C1 Mod will display the percentage of analog output
(UO-07).
MIN OFF Timer reflects the 5 minutes the compressor
must be off before restarting.
MIN ON Timer reflects the 5 minutes the compressor must
be on before shutdown.
Clg to Htg Timer is a 10-minute timer for the heating mode
to cooling mode switchover.
Indicator Lights:
- HP1 EN will light when the enable conditions are met.
- Y1 will light when the UO-10 or compressor #1 is com-
manded on.
- CMP1 will light when the compressor #1 current sensor
show amperage.
- HPS1 and LPS1 will light in their normal state (N.C.).
When they go into alarm the light will go off.
- AHTG will light when the auxiliary heat is on”, all
compressors will shut down.
- EHTG will light when the emergency heat is “on” and
the heat pump 1 shut down.
- WFS will light when there is water flow (used on 62W
units only).
- WFRZ will light when the water freeze stat is closed or
normal state (used on 62W units only).
- DR1 will light when the defrost relay is activated (used
on 62H units only).
Set Points Screens
The set points screen can be access form Home screen
(Home
Stp/DB) or Tech Setting screen (Setup
Setpoint/DB)
and contains links to all available component, safety, and mode set
point screens. See Fig. 18.

Table of Contents

Related product manuals