21
DEADBAND:
SAT - The upper and lower deadband for the heating supply air
temperature.
Heat Pump Heating Set Points
(62W and 62H Only)
The Heat Pump set points screen (Home
Stp/DB
HP1 SP or
HP2 SP) displays the set points and for the heat pump and heat
pump heating mode. See Fig. 25.
Fig. 25 — HP 1 SP
The following set points may be displayed on the HP SP/DB
screen:
HEAT PUMP 1 AND 2 ENABLE:
• OAT - Heat pump heating mode is enabled when the out-
door air temp is below set point
• OAT vs SAT - Heat pump heating is enabled when the out-
door air temp is below the heating supply air temp set point.
• ECAT - for units with ERV. Operation is based upon enter-
ing coil (EC) conditions, which is the per-treated outdoor air
HEATING:
• SAT - In heat pump heating mode, the unit will operate the
compressors to maintain the heat pump heating supply air
temperature set point.
• ZAT - Used for zone air temp override. When the ZAT is
below set point, unit will enter ZAT/SAT override.
DEADBAND:
SAT - The upper and lower deadband for the heating supply air
temperature.
Limits/Safety Set Points
The Limits and Safeties set points screen (Home
Stp/DB
Lim/
Safety) displays set points for unit safeties, including lockouts and
freeze protection. See Fig. 26.
Fig. 26 — Limit/Safety SP/DB
The following set points may be displayed on the Limit/Safety SP
screen:
CLG MODE LO LIMIT:
• OAT - disables cooling mode when the outdoor air temp is
below set point
• ECAT - For units with ECW, disables cooling mode when
the entering coil air temp (pre-treated outdoor air leaving
ECW) is below set point
DH MODE LO LIMIT:
• OAT - disables dehum mode when the outdoor air temp is
below set point
• ECAT - For units with ECW, disables cooling mode when
the entering coil air temp (pre-treated outdoor air leaving
ECW) is below set point
HTG MODE HI LIMIT:
• OAT - disables heat mode when the outdoor air temp is
above set point
• ECAT - For units with ECW, disables heating mode when
the entering coil air temp (pre-treated outdoor air leaving
ECW) is above set point
COMP 1 DISABLE/COMP 2 DISABLE:
• OAT - disables compressor when the outdoor air temp is
below set point
• ECAT - For units with ECW, disables compressor when
the entering coil air temp (pre-treated outdoor air leaving
ECW) is below set point
• OADP - disables compressors when outdoor air dew point
is below set point.
• ECDP - For units with ECW, disables compressor when
the entering coil air dew point (pre-treated outdoor air
leaving ECW) is below set point
UPPER FREEZE:
• DX LAT - After a lower freeze trip and a 5 minute mini-
mum off cycle, the unit will enable compressor operation
after the DX LAT increases above the upper freeze set
point. There is a 5 minute minimum off cycle.
MIDDLE FREEZE:
• DX LAT - When the DX LAT drops below the middle
freeze set point, the compressor will unload.
LOWER FREEZE:
• DX LAT - When the DX LAT drops below the lower
freeze set point for a period of 10 minutes, the compressor
is disabled until the DX LAT rises above the upper freeze
set point
ECW DEFROST:
• WExAT - when the wheel exhaust air temp drops below
this temperature, the ECW slows to prevent frosting.
Unoccupied Setpoints (Units with Night Setback
ETO only)
The Unoccupied set points screen (Home
Stp/DB
Unoc SP)
displays the set points for unoccupied operation. See Fig. 27.