88
Local OAT/OARH Sensor
Enabled
R/W local_oa_sens_en BV 1115
Read/write to Enable the Local OAT/OARH sensor.
LPS #1 Status R lps1_stat BV 225 Low Pressure Switch #1 Status.
LPS #2 Status R lps2_stat BV 228 Low Pressure Switch #2 Status.
LPS1 ALARM R lps1_alarm BV 869 The current Low Pressure Switch #1 Alarm Status.
LPS1 STOP R lps1_stop_alarm BV 870 The current Low Pressure Switch #1 Stop Alarm Status.
LPS2 ALARM R lps2_alarm BV 883 The current Low Pressure Switch #2 Alarm Status.
LPS2 STOP R lps2_stop_alarm BV 884 The current Low Pressure Switch #2 Stop Alarm Status.
LSAT ALARM R low_sat_alarm BV 898 The current Low Supply Air Temperature Alarm Status.
MARH FAIL R marh_failure BV 828 The current MARH Sensor Alarm status.
MA-RH Status R marh_stat AV 224 The Current Mixed Air Relative Humidity Status (MARH).
MAT FAIL R mat_failure BV 827 The current MAT Sensor Alarm status.
MAT Status R mat_stat AV 223 The current Mixed Air Temperature (MAT).
Mixed Air Dew Point R ma_dewpoint AV 264 The current Mixed Air Dew Point Status
Mixed Air Enthalpy R ma_enthalpy AV 265 The current Mixed Air Enthalpy Status
Night Setback Mode ON R nsb_on BV 219 This point displays the status of the Night Setpoint Mode.
NOT ECON R not_econ_fdd BV 961 The current FDD Alarm is not Economizing when it should.
OA AMS SP R/W oa_ams_sp AV 306
The setpoint for Outdoor Air Monitoring Station (Default is
800cfm)
OA Damper Enable R oada_en BV 242 Outdoor Air Damper Enable Code Status
OADA ALARM R oada_alarm BV 950 The current Outside Air Damper Actuator Alarm Status.
OADA HAND R oada_hand_alarm BV 951 The current Outside Air Damper Actuator Hand Alarm Status.
OADA Minimum Position R/W
oada_min_pos_cm
d
AV 607
Read/write Outside Air Damper Minimum Position.
OADA PID Output
Override
R/W oada_pid_ovrd AV 609
Read/write OADA PID Output for CAV (Percentage)
OADA PID Output
Override Lock
R/W
oada_pid_ovrd_loc
k
BV 601
Read/write Outside Air Damper PID Output in Constant Air
Volume (CAV) Status.
OADA Position R oada_pos AV 204 The current Outside Air Damper Position Feedback.
OADA Status R oada_stat BV 220 Outdoor Air Damper Actuator Auxiliary Status.
OARH FAIL R oarh_failure BV 836 The current MAT Sensor Alarm status.
OARH from BAS R/W bas_oarh AV 1106 Read/write Outside Air Relative Humidity Supplied By BAS.
OA-RH Status R oarh_stat AV 229
The Current Outdoor Air Relative Humidity Sensor Status
(OARH).
OAT FAIL R oat_failure BV 835 The current OAT Sensor Alarm status.
OAT from BAS R/W bas_oat AV 1104 Read/write Outside Air Temperature Supplied by BAS.
OAT Status R oat_stat AV 227 The Current Outside Air Temperature Status (RAT).
Occupancy Control
Options
R/W occ_ctrl_opts MSV 101
Read/write point will set the unoccupied/occupied control to
local,BAS,24/7,S/S switch, CO
2
mode.
Occupancy Status R occ_status BV 105 This point gives you the unoccupied/occupied status of the unit.
Occupied Cooling Mode
Low Limit
R/W clg_llim AV 319
The setpoint for Occupied Low Limit Cooling Temperature.
(Default is 55°F)
OD Command R od_cmd BV 1120 Outside Damper Start Command (BO-6).
Operating Condition R op_cond AV 111
This point is a multistat and Table 1 must be used to cross
reference the number to Condition.
Operating Mode R op_mode AV 112
This point is a multistat and Table 2 must be used to cross
reference the number to Operating Mode.
Optimal Start On R opt_start_on BV 902 The current Optimal Start Status.
Outside Air Dew Point R oa_dewpoint AV 266 The current Outside Air Dew Point Status
Outside Air Enthalpy R oa_enthalpy AV 267 The current Outside Air Enthalpy Status
RADA NOT R rada_not_mod_fdd BV 963
The current FDD Alarm the Dampers are Mechanically
Disconnected.
RADA Position R rada_pos AV 601 The current Return Air Damper Actuator Position.
RADA Status R rada_stat AV 283 The current Return Air Damper Actuator Position Status
RARH FAIL R rarh_failure BV 834 The current RARH Sensor Alarm status.
RA-RH Status R rarh_stat AV 226 The current Return Air Humidity (RARH).
RAT FAIL R rat_failure BV 833 The current RAT Sensor Alarm status.
RAT Status R rat_stat AV 225 The current Return Air Temperature Sensor Status (RAT).
Return Air Damper
Status
R rada_cmd BV 503
The current Return Air Damper Status
Return Air Dew Point R ra_dewpoint AV 268 The current Return Air Dew Point Status
Return Air Enthalpy R ra_enthalpy AV 269 The current Return Air Enthalpy Status
RH CMD R rh_cmd BV 564 HGRH Start Command (BO-4).
RH in Cooling R/W rh_clg_mode BV 561 Read/write point Enables Reheat in Cooling Mode.
RV CMD R rv_cmd BV 550 The Reversing Valve Start Command (BO-5).
S/S Switch Status R ss_sw_stat BV 236 Start/Stop Switch Status (N.O.).
SARH FAIL R sarh_failure BV 840 The current SARH Sensor Alarm status.
SARH Status R sarh_stat AV 237 The current Supply Air Relative Humidity Sensor Status (SARH).
SAT FAIL R sat_failure BV 839 The current SAT Sensor Alarm status.
SAT Heat Fail SP R/W sat_heat_fail_sp AV 361
The setpoint for Supply Air Temperature Heat Failure Alarm
(Default is 50°F).
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air (cont)
Display Name Read/Write
BACnet
Description
Reference Name Type ID