89
SAT High Limit SP R/W sat_high_limit_sp AV 362
The setpoint High Supply Air Temperature alarm (Default is
120°F).
SAT Low Limit SP R/W sat_low_limit_sp AV 808
The setpoint for Low Supply Air Temperature Alarm (Default is
40°F).
SAT Maximum Reset R/W sat_max_reset AV 326
Read/write for the SAT Maximum for the ZAT/SAT reset Option
(Default is 15).
SAT Ratio R/W sat_ratio AV 325
Read/write for the SAT ratio for the ZAT/SAT reset Option
(Default is 3).
SAT Status R sat_stat AV 235 The current Supply Air Temperature (SAT).
SC ZAT DISA R/W sc_zat_disa BV 1110 Read/write to Enable the ZAT control of the SC.
SD ALARM R sd_alarm BV 896 The current Smoke Detector Alarm Status.
SD Status R sd_stat BV 235 Smoke Detector Switch Status (N.C.).
SF ALARM R sf_alarm BV 855 The current Supply Fan Alarm Status.
SF AMS SP R/W sf_ams_sp AV 304
The setpoint for Supply Fan Air Monitoring Station (Default is
3900cfm)
SF AMS Status R sf_ams_stat AV 261 The current Supply Fan Air Monitoring Staion Status
SF Command R sf_cmd BV 241 Supply Fan Start Command (BO-1).
SF DPT SP R/W sf_dpt_sp AV 301
The setpoint for Supply Fan Duct Pressure Transducer (Default 1
in. of H
2
O).
SF DPT Status R sf_dpt_stat AV 255
The current Supply Fan Duct Pressure Transducer Status
(Default 5 in. of H
2
O).
SF HAND R sf_hand_alarm BV 856 The current Supply Fan Hand Alarm Status.
SF Mod. CLG Min. Output R/W sf_clg_min_out AV 630
Read/write point for Supply Fan Modulation Minimum % for
Cooling Operation (Default is 50%).
SF Mod. HP Min. Output R/W sf_hp_min_out AV 629
Read/write point for Supply Fan Modulation Minimum % for Heat
Pump Operation (Default is 85%).
SF Modulation R sfmod_pct AV 282 The current Supply Fan Modulation Status (UO-1 Percentage).
SF Operation R/W sf_oper MSV 931
Read/write point to set Occupied/unoccupied for the Supply Fan
Operation (1=Continuous/Demand, 2=Con/Con, and 3= Dem/
Dem).
SF PID Output Override R/W sf_pid_ovrd AV 628 Read/write Supply Fan PID Output for CAV (Default is 90%).
SF PID Output Override
Lock
R/W sf_pid_ovrd_lock BV 621
Read/write Supply Fan PID Output in Constant Air Volume (CAV)
Status.
SF-APS or CS Status R sf_aps_stat BV 223 Supply Fan Air Proven or Current Sensor Status.
SFMinimum Output R sf_min_out AV 627 The setpoint for Supply Fan Minimum Output (50%).
SLT #1 Status R slt_stat AV 250 The current Suction Line Temperature for circuit #1 (SLT1).
SLT #2 Status R slt2_stat AV 251 The current Suction Line Temperature for circuit #2 (SLT2).
SLT FAIL R slt_failure BV 845 The current SLT Sensor Alarm status.
SLT2 FAIL R slt2_failure BV 846 The current SLT2 Sensor Alarm status.
Sub-Cooling Command R sc_cmd BV 248 Sub-Cooling Start Command (BO-8)
Supply Air Dew Point R sa_dewpoint AV 270 The current Supply Air Dew Point Status
Supply Air Enthalpy R sa_enthalpy AV 271 The current Supply Air Enthalpy Status
Unit Stop R unit_stop BV 819 The current Unit Stop Status.
Unoccupied Cooling
Mode Low Limit
R/W clg_llim_u AV 320
The setpoint for Unoccupied Low Limit Cooling Temperature.
W1 Command R w1_cmd BV 240 The Heating #1 Start Command (BO-5).
W1 Enable R w1_en BV 578 The current Heating #1 Enable Status.
W2 Command R w2_cmd BV 239 The Heating #2 Start Command (UO-6).
WExAT FAIL R wexat_failure BV 837 The current WExAT Sensor Alarm status.
WExAT Status R wexat_stat AV 238 The current Wheel Exiting Air Temperature (WExAT).
WExRH FAIL R wexrh_failure BV 838 The current WexRH Sensor Alarm status.
WExRH Status R wexrh_stat AV 239 The current Wheel Exiting Air Humidity (WExRH).
WFS ALARM R wfs_alarm BV 829 The current Water Flow Switch Alarm status.
WFS Status R wfs_stat BV 230 Water Flow Switch Status in WSHP (N.O.).
ZAT FAIL R zat_failure BV 852 The current ZAT Sensor Alarm status.
ZAT From BAS R/W zat_bas AV 208
The current Zone Air Temperature (ZAT) written to the controller
by the BAS system.
ZAT Ratio R/W zat_ratio AV 324
Read/write for the ZAT ratio for the ZAT/SAT reset Option
(Default is 1).
ZAT Status R zat_stat AV 209 The current Zone Air Temperature (ZAT) from the Zs sensor.
ZAT/SAT Set Point Reset
Enable
R/W rs_sat_en BV 301
Read/writable point to enable ZAT/SAT Temperature Reset
Option.
ZN DPT SP R/W zn_dpt_sp AV 303
The setpoint for Zone Duct Pressure Transducer (Default is
0.020 in. of H
2
O)
Zone Air Dew Point R za_dewpoint AV 274 The current Zone Air Dew Point Status
Zone Air Enthalpy R za_enthalpy AV 275 The current Zone Air Enthalpy Status
Zone Set Points R/W clg_zat_sp_o AV 200
The setpoint for Zone Temperature Setpoint for occupied cooling
resides in the Setpoint Microblock (Default is 74°F).
Zone Set Points R/W htg_zat_sp_o AV 201
The setpoint for Zone Temperature Setpoint for occupied heating
resides in the Setpoint Microblock (Default is 68°F).
Zone Set Points R/W clg_zat_sp_u AV 202
The setpoint for Zone Temperature Setpoint for unoccupied
cooling resides in the Setpoint Microblock (Default is 8F).
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air (cont)
Display Name Read/Write
BACnet
Description
Reference Name Type ID