90
LEGEND FOR PAGES 85-90
Zone Set Points R/W htg_zat_sp_u AV 203
The Zone Temperature Setpoint for unoccupied heating resides
in the Setpoint Microblock (Default is 60).
ZRH FAIL R zrh_failure BV 853 The current ZRH Sensor Alarm status.
Z-RH From BAS R/W zrh_bas AV 211
The current Zone Air Humidity (Z-RH) written to the controller by
the BAS system.
Z-RH Status R zrh_stat AV 212 The current Zone Air Humidity (Z-RH) from the ZS sensor.
Table C — Mapping Points - Carrier 62X Rev. H - 100% Outdoor Air Air-to-Air (cont)
Display Name Read/Write
BACnet
Description
Reference Name Type ID
OEM — Automated Logic Incorporated, a division of Carrier
APS — Air Pressure Switch
BAS — Building Automation System
CCS — Compressor Current Switch
CFI — Clogged Filter Indicator
CM1A — Compressor #1
CC1A — Compressor #1 Contactor Coil
CC1A-A1 — Compressor #1 Auxiliary Contact
CFM — Cubic Feet per Minute (volumetric flow rate)
CPM — Compressor Protection Module
CM2A — Compressor #2
CC2A — Compressor #2 Contactor Coil
CC2A-A1 — Compressor #2 Auxiliary Contact
DCM — Digital Compressor Module
DPT — Differential Pressure Transmitter
DOAU — Dedicated Outdoor Air Unit
DOM — Delay-On-Make
EC-RH — Entering Coil Relative Humidity, measured before
entering the DX coil and after the ERV
ECAT — Entering Coil Air Temperature, measured before
entering the DX coil and after the ERV
ERV — Energy Recovery Ventilator
EMR — Energy Management Relay; normally closed contact
EF — Exhaust Fan
EF-APS — Exhaust Fan Air Pressure Switch
EF-DPT — Differential Pressure Transmitter
EF-VFD — Exhaust Fan Variable Frequency Drive
FPM — Feet per Minutes (velocity)
FSC — Fan Speed Control
HAR — Heating Analog Relay
HARM — Heating Analog Relay Module
HGRH — Hot Gas Reheat
HPS — High Pressure Switch
HP1 — High Pressure Switch #1
HP2 — High Pressure Switch #2
LA — Low Ambient Pressure Sensor
LAT — Leaving Air Temperature
LP1 — Low Pressure Switch #1
LP2 — Low Pressure Switch #2
MDC — Modulating Discharge Controller
MDV — Modulating Discharge Valve
MRC — Modulating Reheat Controller
MRV — Modulating Reheat Valve
NC — Normally Closed contact
NO — Normally Opened contact
OA — Outside Air; prior to any conditioning
OD — Outside Air Damper
OA-RH — Outside Air Relative Humidity (real), measured
before air enters the ERV, if existing
OAT — Outside Air Temperature (real), measured before air
enters the ERV, if existing
OFM1 — Outdoor Fan #1 Motor
OF1C — Outdoor Fan #1 Contactor Coil
OF1-
VFD
— Outdoor Fan #1 Variable Frequency Drive
OFM2 — Outdoor Fan #2 Motor
OF2C — Outdoor Fan #2 Contactor Coil
OF2-
VFD
— Outdoor Fan #2 Variable Frequency Drive
RHR — Reheat Relay
RHS — Reheat Valve Solenoid
RTHO — Room Temperature Heating Override
RTRHO — Room Temperature Reheat Override
SD — Smoke Detector; normally closed contact
SF — Supply Fan
SF-APS — Supply Fan Air Pressure Switch
SF-DPT — Differential Pressure Transmitter
SF-VFD — Supply Fan Variable Frequency Drive
SLT — Suction Line Temperature, attached to the suction
line near the suction header of the DX coil
VFD — Variable Frequency Drive
WM — Wheel Motor
WMC — Wheel Motor Contactor
WM-VFD — Wheel Motor Variable Frequency Drive
ZAT — Zone Air Temperature
Z-RH — Zone Relative Humidity