28
4 - PHYSICAL AND ELECTRICAL DATA 61WG/30WG/30WGA
30WGA 20 25 30 35 40 45 50 60 70 80 90
Operating weight
(1)
kg 164 171 171 177 180 185 321 324 332 339 354
Sound levels
(2)
Sound power level, standard unit dB(A) 67,0 68,5 69,0 69,3 70,0 70,1 71,5 72,0 72,0 73,0 73,4
Compressors Hermetic scroll 48,3 r/s
Quantity 1 1 1 1 1 1 2 2 2 2 2
Number of capacity steps 1 1 1 1 1 1 2 2 2 2 2
Minimum capacity % 100 100 100 100 100 100 50 50 50 50 50
Refrigerant
(1)
R-410A
Oil 160SZ
Charge per compressor l 3 3,3 3,3 3,3 3,3 3,6 3,3 3,3 3,3 3,3 3,6
Control TouchPilot Junior
Evaporator Direct-expansion plate heat exchanger
Water volume l 3,3 3,6 3,6 4,2 4,6 5,0 8,4 9,2 9,6 10,4 12,5
Water connections Victaulic
Inlet/outlet in 1,5 1,5 1,5 1,5 1,5 1,5 2 2 2 2 2
Max, water-side operating pressure without hydraulic module
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Refrigerant connections
Discharge line diameter in 7/8 7/8 7/8 7/8 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
Liquid line diameter in 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8
30WGA 110 120 140 150 170 190
Operating weight
(1)
kg 630,3 646,6 665,0 750,9 773,7 796,4
Sound levels
(2)
Sound power level, standard unit dB(A) 75,5 76,5 77,8 76,0 77,0 78,4
Compressors Hermetic scroll 48,3 r/s
Quantity 3 3 3 4 4 4
Number of capacity steps 3 3 3 4 4 4
Minimum capacity % 33 33 33 25 25 25
Refrigerant
(1)
R-410A
Oil 160SZ
Charge per compressor l 3,3 3,3 3,6 3,3 3,3 3,6
Control TouchPilot Junior
Evaporator Direct-expansion plate heat exchanger
Water volume l 15,18 17,35 19,04 23,16 26,52 29,05
Water connections Victaulic
Inlet/outlet in 1''5/8 1''5/8 1''5/8 1''5/8 1''5/8 1''5/8
Max, water-side operating pressure without hydraulic module
kPa 1000 1000 1000 1000 1000 1000
Condenser Plate heat exchanger
Net water volume l 15,18 17,35 19,04 23,16 26,52 29,05
Water connections Victaulic
Inlet/outlet in 1''3/8 1''3/8 1''3/8 1''1/8 1"1/8 1"1/8
Max, water-side operating pressure without hydraulic module
kPa 1000 1000 1000 1000 1000 1000
Refrigerant connections
Discharge line diameter in 1''3/8 1''3/8 1''3/8 1''1/8 1''1/8 1''1/8
Liquid line diameter in 7/8'' 7/8'' 7/8'' 7/8'' 7/8'' 7/8''
(1) Weight shown is a guideline only. Please refer to the unit nameplate
(2) In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in
accordance with ISO 9614-1.