EasyManua.ls Logo

Carrier AquaSnap 61WG Series - Electrical Data, Optional Hydraulic Module

Carrier AquaSnap 61WG Series
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
4 - PHYSICAL AND ELECTRICAL DATA 61WG/30WG/30WGA
4.5 - Electrical data, optional hydraulic module
The pumps that are factory-installed in these units have motors with efciency class IE3. The additional electrical data required
(1)
is as follows:
Motors of xed-speed hydraulic module pumps, 61WG/30WG/30WGA (options 116T and 270T)
No.
(2)
Description
(3)
61WG/30WG/30WGA - options 116T and 270T (low-pressure pumps)
20 25 30 35 40 45 50 60 70 80 90
1
Nominal efciency at full load and nominal voltage % 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 81,1 83,4
Nominal efciency at 75% rated load and nominal voltage % 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 80,8 81,2
Nominal efciency at 50% rated load and nominal voltage % 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 77,5 78,3
2 Efciency level % IE3
3 Year of manufacture
This information varies depending on the manufacturer and model at the
time of incorporation.
Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial
registration number and place of manufacturer
5 Product's model number
6 Number of motor poles 2 2 2 2 2 2 2 2 2 2 2
7-1
Rated shaft power output at full load and nominal voltage
(400 V)
kW 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 0,8 1,3
7-2 Maximum power input (400 V)
(4)
kW 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,1 1,6
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50
9-1 Rated voltage V 3x400
9-2 Maximum current drawn (400 V)
(5)
A 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,1 2,9
10 Rated speed
r/s 2850 2850 2850 2850 2850 2850 2850 2850 2850 2850 2890
rpm 47 47 47 47 47 47 47 47 47 47 48
11 Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specically designed
I- Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
IV - Maximum air temperature
Please refer to the operating conditions given in this manual or in the
specic conditions in the Carrier selection programs.
V - Potentially explosive atmospheres Non-ATEX environment
Motors of variable-speed hydraulic module pumps, 61WG/30WG/30WGA (options 116V and 270V)
No.
(2)
Description
(3)
61WG/30WG/30WGA - options 116V and 270V (high-pressure pumps)
20 25 30 35 40 45 50 60 70 80 90
1
Nominal efciency at full load and nominal voltage % 83,4 83,4 83,4 83,4 83,4 83,4 84,8 84,8 84,8 84,8 84,8
Nominal efciency at 75% rated load and nominal voltage % 81,2 81,2 81,2 81,2 81,2 81,2 82,2 82,2 82,2 82,2 82,2
Nominal efciency at 50% rated load and nominal voltage % 78,3 78,3 78,3 78,3 78,3 78,3 79 79 79 79 79
2 Efciency level % IE3
3 Year of manufacture
This information varies depending on the manufacturer and model at the
time of incorporation.
Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial
registration number and place of manufacturer
5 Product's model number
6 Number of motor poles 2 2 2 2 2 2 2 2 2 2 2
7-1
Rated shaft power output at full load and nominal voltage
(400 V)
kW 1,3 1,3 1,3 1,3 1,3 1,3 1,7 1,7 1,7 1,7 1,7
7-2 Maximum power input (400 V)
(4)
kW 1,6 1,6 1,6 1,6 1,6 1,6 2,4 2,4 2,4 2,4 2,4
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50
9-1 Rated voltage V 3x400
9-2 Maximum current drawn (400 V)
(5)
A 2,9 2,9 2,9 2,9 2,9 2,9 4,2 4,2 4,2 4,2 4,2
10 Rated speed
r/s 2890 2890 2890 2890 2890 2890 2870 2870 2870 2870 2870
rpm 48 48 48 48 48 48 48 48 48 48 48
11 Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specically designed
I- Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
IV - Maximum air temperature
Please refer to the operating conditions given in this manual or in the
specic conditions in the Carrier selection programs.
V - Potentially explosive atmospheres Non-ATEX environment
(1) Required by regulation 640/2009 with regard to the application of directive 2008/28/EC on the eco-design requirements for electric motors
(2) Item number imposed by regulation 640/2009, annex I2b.
(3) Description given by regulation 640/2009, annex I2b.
(4) To obtain the maximum power input for a unit with hydraulic module add the maximum unit power input from the electrical data table to the pump power input.
(5)
To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.