6 - ELECTRICAL CONNECTION
6.1 - Electrical connections, control box
18
18
79
26
S
1
1
PE
Legend
1 Main disconnect switch
PE Earth connection
S Power supply cable section (see table “Recommended wire sections”).
NOTES:
The units have only one power connection point located at the
main disconnect switch.
Before connecting electric power cables, it is imperative to check
the correct order of the 3 phases (L1 - L2 - L3).
Non-certied drawings.
Refer to the certied dimensional drawings.
Before connecting the unit check that the phase order in the
customer control box is the same as shown in the customer wiring
diagrams.
6.2 - Power supply
The  power  supply  must  conform  to  the  specication  on  the  unit 
nameplate. The supply voltage must be within the range specied in 
the electrical data table. For connections refer to the wiring diagrams.
WARNING: Operation of the unit with an incorrect supply
voltage orexcessive phase imbalanceconstitutes abuse
which will invalidate the warranty. If the phase imbalance
exceeds2%forvoltage,or10%forcurrent,contactyourlocal
electricity supply at once and ensure that the unit is not
switched on until corrective measures have been taken.
6.3 - Voltage phase imbalance (%)
100 x max. deviation from average voltage
Average voltage
Example:
On a 400 V - 3 ph - 50 Hz supply, the individual phase voltages
were measured to be:
AB = 406 V ; BC = 399; AC = 394 V
Average voltage = (406 + 399 + 394)/3 = 1199/3
= 399.7 say 400 V
Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6
The maximum deviation from the average is 6 V. The greatest
percentage deviation is: 100 x 6/400 = 1.5 %
This is less than the permissible 2% and is therefore acceptable.
6.4 - Recommended wire sections
Wire sizing is the responsibility of the installer, and depends on the
characteristics and regulations applicable to each installation site. The
following is only to be used as a guide-line, and does not make the
manufacturer in any way liable. After wire sizing has been completed,
using the certied dimensional drawing, the installer must ensure easy 
connection and dene any modications necessary on site.
The connections provided as standard for the eld-supplied power
entry cables to the general disconnect/isolator switch are designed
for the number and type of wires, listed in the table on the next page.
The calculations are based on the maximum machine current (see
electrical data tables). For the design the following standardised
installation methods are used, in accordance with IEC 60364, table 52C:
- For units installed inside the building:
- No.13: perforated horizontal cable conduit, and No. 41: closed
conduit.
The calculation is based on PVC or XLPE insulated cables with
copper or aluminium core. A maximum ambient temperature of 40
°C has been taken into account. The given wire length limits the
voltage drop to < 5%.
IMPORTANT:Beforeconnectionofthemainpowercables(L1-L2
-L3)ontheterminalblock,itisimperativetocheckthecorrect
order of the 3 phases before proceeding to the connection on
then terminal block or the main disconnect/isolator switch.
6.4.1 - Field control wiring
IMPORTANT: Field connection of interface circuits may lead
tosafetyrisks:anycontrolboxmodicationmustmaintain
equipment conformity with local regulations. Precautions
must be taken to prevent accidental electrical contact between
circuits supplied by different sources:
- The routing selection and/or conductor insulation
characteristics must ensure dual electric insulation.
- In case of accidental disconnection, conductorxing
betweendifferentconductorsand/orinthecontrolbox
prevents any contact between the conductor ends and an
active energised part.
RefertotheTouchPilotJuniorControlsIOMandthecertied
wiring diagramsupplied with theunit for the eld control
wiring of the following features:
- Remote on/off switch
- Remote heat/cool switch
- Demandlimitexternalswitch1
- Remote dual set point
- Alarm report
- Pump control - unit without hydraulic module.
- Relief boiler or electric heater
- Valve control - see description of options 153 and 154 in
the TouchPilot Junior controls manual