4 - PHYSICAL AND ELECTRICAL DATA 61WG/30WG/30WGA
30WGA without hydraulic module 20 25 30 35 40 45 50 60 70 80 90
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)
(1)
Standard unit A 98,0 142,0 142,0 147,0 158,0 197,0 161,0 162,0 170,0 183,0 226,0
Unit with electronic starter option A 53,9 78,1 78,1 80,9 86,9 108,4 96,8 97,9 104,1 112,3 137,4
Unit power factor at maximum capacity
(2)
0,9 0,8 0,9 0,9 0,9 0,9 0,8 0,9 0,9 0,9 0,9
Maximum operating power input
(2)
kW 9,2 10,8 11,7 13,7 15,1 17,1 21,5 23,3 27,3 30,3 34,2
Nominal unit operating current draw
(3)
A 11,4 13,8 14,7 16,5 18,1 21,2 27,6 29,4 33,1 36,4 42,5
Maximum operating current draw (Un)
(4)
A 15,6 18,7 19,8 23,2 25,4 29,0 37,4 39,6 46,4 50,8 58,0
Maximum operating current draw (Un-10%)
A 17,3 20,8 22,0 25,8 28,2 32,2 41,6 44,0 51,6 56,4 64,4
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection See table below "Short-circuit stability current"
30WGA without hydraulic module 110 120 140 150 170 190
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)
(1)
Standard unit A 193,4 208,8 255 216,6 234,2 284
Unit with electronic starter option A 127,3 137,7 166,4 150,5 163,1 195,4
Unit power factor at maximum capacity
(2)
0,87 0,85 0,85 0,87 0,85 0,85
Maximum operating power input
(2)
kW 41 45 51 55 60 68
Nominal unit operating current draw
(3)
A 49,5 54,3 63,6 66 72,4 84,8
Maximum operating current draw (Un)
(4)
A 69,6 76,2 87 92,8 101,6 116
Maximum operating current draw (Un-10%)
(5)
A 77,3 84,7 96,7 103,1 112,9 128,9
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection See table below "Short-circuit stability current"
(1) Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + locked rotor current or limited start-up
current of the largest compressor).
(2) Maximum power input at the unit operating limits.
(3) Values obtained at the following conditions: evaporator entering/leaving water temperature 12 °C/7 °C. condenser entering/leaving water temperature 45 °C.
(4) Maximum unit operating current at maximum unit power input and 400 V.
(5) Maximum unit operating current at maximum unit power input and 360 V.
4.4 - Short-circuit stability current (TN system
(1)
) - standard unit (with main disconnect switch)
61WG/30WG/30WGA 20 25 30 35 40 45 50 60 70 80 90
Value with non-specied upstream protection
Short-term current at 1 s - Icw kA rms 3 3 3 3 3 3 3 3 3 3 3
Admissible peak current - Ipk kA pk 6 6 6 6 6 6 6 6 6 6 6
Maximum value with upstream protection (by circuit breaker)
Conditional short-circuit current Icc kA rms 40 40 40 40 40 40 40 40 40 40 40
Schneider circuit breaker - Compact series NSX 100N
Reference number
(2)
LV429795
61WG/30WG/30WGA 110 120 140 150 170 190
Value with non-specied upstream protection
Short-term current at 1 s - Icw kA rms 5,5 5,5 5,5 5,5 5,5 5,5
Admissible peak current - Ipk kA pk 20 20 20 20 20 20
Maximum value with upstream protection (by circuit breaker)
Conditional short-circuit current Icc kA rms 154 154 154 154 154 154
Schneider circuit breaker - Compact series NSX 100N
Reference number
(2)
LV429795
(1) Earthing system type
(2)  If  another  current  limitation  protection  system is  used, its  time-current and  thermal constraint  (I²t) trip  characteristics must  be at  least equivalent  to those  of the 
recommended Schneider circuit breaker.
The short-circuit stability current values above are suitable with the TN system.