4 - PHYSICAL AND ELECTRICAL DATA 61WG/30WG/30WGA
61WG without hydraulic module 110 120 140 150 170 190
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)
(1)
Standard unit A 195,8 211,4 258,8 220,2 238,1 289,7
Unit with electronic starter option A 129,7 140,3 170,2 154,1 167,0 201,1
Unit power factor at maximum capacity
(2)
0,87 0,85 0,85 0,87 0,85 0,85
Maximum operating power input
(2)
kW 44 47 55 59 63 73
Nominal unit operating current draw
(3)
A 45,6 49,5 59,1 60,8 66 78,8
Maximum operating current draw (Un)
(4)
A 73,2 80,1 92,7 97,6 106,8 123,6
Maximum operating current draw (Un-10%)
(5)
A 81,3 89,0 103,0 108,4 118,7 137,3
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection See table below "Short-circuit stability current"
(1) Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + locked rotor current or limited start-up
current of the largest compressor).
(2) Maximum power input at the unit operating limits.
(3)
Values obtained at standardised Eurovent conditions: evaporator entering/leaving water temperature 10 °C/7 °C. condenser entering/leaving water
temperature 30 °C/35 °C.
(4) Maximum unit operating current at maximum unit power input and 400 V.
(5) Maximum unit operating current at maximum unit power input and 360 V.
30WG without hydraulic module 20 25 30 35 40 45 50 60 70 80 90
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)
(1)
Standard unit A 98,0 142,0 142,0 147,0 158,0 197,0 161,0 162,0 170,0 183,0 226,0
Unit with electronic starter option A 53,9 78,1 78,1 80,9 86,9 108,4 96,8 97,9 104,1 112,3 137,4
Unit power factor at maximum capacity
(2)
0,9 0,8 0,9 0,9 0,9 0,9 0,8 0,9 0,9 0,9 0,9
Maximum operating power input
(2)
kW 9,2 10,8 11,7 13,7 15,1 17,1 21,5 23,3 27,3 30,3 34,2
Nominal unit operating current draw
(3)
A 10,5 13,2 13,8 15,6 16,2 20,2 26,4 27,6 31,2 32,4 40,4
Maximum operating current draw (Un)
(4)
A 15,6 18,7 19,8 23,2 25,4 29,0 37,4 39,6 46,4 50,8 58,0
Maximum operating current draw (Un-10%)
†
A 17,3 20,8 22,0 25,8 28,2 32,2 41,6 44,0 51,6 56,4 64,4
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection See table below "Short-circuit stability current"
30WG without hydraulic module 110 120 140 150 170 190
Power circuit
Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V, via internal transformer
Maximum start-up current draw (Un)
(1)
Standard unit A 193,4 208,8 255,0 216,6 234,2 284,0
Unit with electronic starter option A 127,3 137,7 166,4 150,5 163,1 195,4
Unit power factor at maximum capacity
(2)
0,87 0,85 0,85 0,87 0,85 0,85
Maximum operating power input
(2)
kW 41 45 51 55 60 68
Nominal unit operating current draw
(3)
A 46,8 48,6 60,6 62,4 64,8 80,8
Maximum operating current draw (Un)
(4)
A 69,6 76,2 87,0 92,8 101,6 116,0
Maximum operating current draw (Un-10%)
(5)
A 77,3 84,7 96,7 103,1 112,9 128,9
Customer-side unit power reserve Customer reserve at the 24 V control power circuit
Short-circuit stability and protection See table below "Short-circuit stability current"
(1) Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + locked rotor current or limited start-up
current of the largest compressor).
(2) Maximum power input at the unit operating limits.
(3)
Values obtained at standardised Eurovent conditions: evaporator entering/leaving water temperature 12 °C/7 °C. condenser entering/leaving water temperature 30 °C/ 35 °C.
(4) Maximum unit operating current at maximum unit power input and 400 V.
(5) Maximum unit operating current at maximum unit power input and 360 V