EasyManua.ls Logo

Carrier AquaSnap 61WG Series - 10 Nominal Water Flow Control with Fixed-Speed Pump; General; Water Flow Control Procedure

Carrier AquaSnap 61WG Series
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
10 - NOMINAL WATER FLOW CONTROL WITH FIXED-SPEED PUMP
10.1 - General
The water circulation pumps of the units have been sized to allow
the hydraulic modules to cover all possible congurations based 
on the specic installation conditions, i.e. for various temperature 
differences between the entering and the leaving water (∆T) at full 
load, which can vary between 2.5 and 7 K for evaporators and 3
and 18 K for condensers.
This required difference between the entering and leaving water
temperature determines the nominal system ow rate. It is above 
all absolutely necessary to know the nominal system ow rate to 
allow its control via a manual valve.
Manual control valves for the unit are not supplied and must be
installed upstream and downstream of the evaporator and
condenser water loops to ensure correct ow control. 
With the pressure loss generated by the control valve in the
hydraulic system, the valve is able to impose the system pressure/
ow curve on the pump pressure/ow curve, to obtain the desired 
operating point (see example).
The pressure drop reading in the plate heat exchanger is used to
control  and  adjust the  nominal system ow  rate. The pressure 
drop is measured with the pressure sensors connected to the heat
exchanger water inlet and outlet.
Use this specication  for the unit selection to know  the system 
operating conditions and to deduce the nominal air ow as well 
as the plate heat exchanger pressure drop at the specified
conditions. If this information is not available at the system start-
up, contact the technical service department responsible for the
installation to get it.
These characteristics can be obtained from the technical literature
using the unit performance tables or the Electronic Catalogue
selection program for all conditions.
10.2 - Water ow control procedure
As the total system pressure drop is not known exactly at the
start-up, the water ow rate must be adjusted with the control valve 
to obtain the specic ow rate for this application.
Proceed as follows:
- Open the valve fully.
- Start-up the pump using the forced start command (refer to
the controls manual) and let the pump run for two consecutive
hours to clean the hydraulic circuit of the system (presence
of solid contaminants).
- Read the hydraulic module pressure drop by taking the
difference of the readings at the machine connected to the
hydraulic module inlet and outlet. Compare this value after
two hours of operation.
Entering water pressure reading
FF
O
Leaving water pressure reading
O
F
F
Legend
O Open
F Closed
Water inlet
Water outlet
Pressure gauge
If the pressure drop has increased, this indicates that the screen
lter  must  be  removed  and  cleaned,  as  the  hydraulic  circuit 
contains solid particles. In this case, in units with option 293 or
293A, close the shutoff valves at the water inlet and outlet and
remove the screen lter after emptying the hydraulic section of 
the unit. In units without option 293 or 293A, clean the screen lter 
on hydraulic circuit out of the unit.
Renew, if necessary, to ensure that the lter is not contaminated.
When the circuit is cleaned, read the pressures at the unit (entering
water pressure - leaving water pressure), expressed in kPa to nd 
out the plate heat exchanger pressure drop.
Compare the value obtained with the theoretical selection value.
If the pressure drop measured is higher than the value specied 
this means that the ow rate in the plate heat exchanger (and thus 
in the system) is too high. The pump supplies an excessive ow 
rate based on the global pressure drop of the application. In this
case close the control valve one turn and read the new pressure
difference.
Proceed by successively closing the control valve until you obtain
the specic pressure drop that corresponds to the nominal ow 
rate at the required unit operating point.
If the system has an excessive pressure drop in relation to the
available static pressure provided by the pump, the resulting water
ow rate will be reduced and the difference between entering and 
leaving water temperature of the hydraulic module will be
increased.

Table of Contents

Related product manuals