35
4 - PHYSICAL AND ELECTRICAL DATA 61WG/30WG/30WGA
Motors of variable-speed hydraulic module pumps, 61WG/30WG (270W)
No.
(2)
Description
(3)
61WG/30WG - options 270W (Dual high-pressure pumps)
110 120 140 150 170 190
1
Nominal efciency at full load and nominal voltage % 87,1 87,1 87,1 88,1 88,1 88,1
Nominal efciency at 75% rated load and nominal voltage % 84,6 84,6 84,6 87,5 87,5 87,5
Nominal efciency at 50% rated load and nominal voltage % 82,5 82,5 82,5 86,5 86,5 86,5
2 Efciency level % IE3 IE3 IE3 IE3 IE3 IE3
3 Year of manufacture
This information varies depending on the manufacturer and model at
the time of incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration
number and place of manufacturer
5 Product's model number
6 Number of motor poles 2 2 2 2 2 2
7-1
Rated shaft power output at full load and nominal voltage (400
V)
kW 3 3 3 4 4 4
7-2 Maximum power input (400 V)
(4)
kW 3,4 3,4 3,4 4,5 4,5 4,5
8 Rated input frequency Hz 50 50 50 50 50 50
9-1 Rated voltage V 400V 3P 400V 3P 400V 3P 400V 3P 400V 3P 400V 3P
9-2 Maximum current drawn (400 V)
(5)
A 6,2 6,2 6,2 7,8 7,8 7,8
10 Rated speed
r/s 48,58333 48,58333 48,58333 48,83333 48,83333 48,83333
rpm 2915 2915 2915 2930 2930 2930
11 Product disassembly, recycling or disposal at end of life
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specically designed
I- Altitudes above sea level m < 1000
(6)
II - Ambient air temperature °C < 40
IV - Maximum air temperature
Please refer to the operating conditions given in this manual or in the
specic conditions in the manufacturer selection programs.
V - Potentially explosive atmospheres Non-ATEX environment
(1) Required by regulation 640/2009 with regard to the application of directive 2009/125/EC on the eco-design requirements for electric motors
(2) Item number imposed by regulation 640/2009, annex I2b.
(3) Description given by regulation 640/2009, annex I2b.
(4) To obtain the maximum power input for a unit with hydraulic module add the maximum unit power input from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current
draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.