ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
32
Wiring and DIP switch configuration 21 AC systems
Outputs
Config. 21:
HC21
Fan VFS, Humidifier,
Reheat for
Dehumidification
11
X
12
Economizer
(5)
(option SW2.6 ON)
13
X
14
Heat element 2
(2nd stage heat)
15
Compressor
(3)
16
Heat element 1
(2)
(1st stage heat)
AO1
Humidifier
AO2
Fan VFS
SW1
SW2
(1)
SW1.1, SW1.2 Fan speeds:
2 speeds (Low and High):
3 speeds (Low, Med., and High):
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 – HP (Heat pump):
HC (not heat pump):
ON = Heat pump active in cool, OFF = Heat pump active in heat
ON = Electrical heater, OFF = Oil/Gas heater (no fan)
(3)
SW1.5 – Compressor delay:
ON = Disable, OFF = Enable
(4)
SW2.3 – Dehumidification:
ON = Use dehumidifier
OFF = Use reheat for dehumidification
(5)
SW2.6 – Terminal 12 operation:
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
See drawing in Wiring terminals and DIP switches (page 23) for DIP switch locations.
Fan VFS, Humidifier: 0-10VDC. 0.5mA Not isolated
Control - Heat elements, Heat pump, Compressors, Economizer: 24VAC, 0.5A max.