ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
56
Technician Settings P83 to P88
P83 – View T2 temperature sensor readings
Note: If T2 is not connected, 0.0 will appear on display
P84 – View T3 temperature sensor readings
Note: If T3 is not connected, 0.0 will appear on display
P85 – De-ice in cool cut-in temperature (AC only)
Range: -9.5…+8°C / 15...46°F
Default: 0°C / 32°F
The indoor unit coil temperature in which de-icing will start.
P86 – De-ice in cool cut-out temperature (AC only)
Range: 2...20°C / 36...68°F
Default: 8°C / 46°F
The indoor unit coil temperature in which de-icing will stop.
P87 – De-ice in heat time (AC only)
Range: 2...7 Minutes
Default: 5 Minutes
The length of de-icing procedure.
P88 – De-ice in heat break time (AC only)
Range: 10… 30 Minutes
Default: 25 Minutes
The time interval between de-icing cycles.