EasyManua.ls Logo

Carrier ComfortVu Plus TBPL-H - Wiring and DIP Switch Configurations 30 to 33 - FC Systems - 4-Pipe

Carrier ComfortVu Plus TBPL-H
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
35
Wiring and DIP switch configurations 30 to 33 FC systems - 4-pipe
Outputs
Config. 30:
4-Pipe, 1/2/3 Speeds
fan
(1)
Config. 31:
4-Pipe, 1/2/3 Speeds
fan
(1)
, Floor heating
Config. 32:
4-Pipe, 1/2/3 Speeds
fan
(1)
, Cool valve PID
Config. 33:
4-Pipe, 1/2/3 Speeds
fan
(1)
, Cool valve PID,
Floor heating
11
Fan high
Fan high
Fan high
Fan high
12
Fan medium
(or Economizer
(5)
)
Fan medium
(or Economizer
(5)
)
Fan medium
(or Economizer
(5)
)
Fan medium
(or Economizer
(5)
)
13
Fan low
Fan low
Fan low
Fan low
14
Heat element
(2)
(2nd stage heat)
Floor heating (1st
stage heat no fan)
Heat element
(2)
(2nd stage heat)
Floor heating (1st
stage heat no fan)
15
Cool valve
(3)
Cool valve
(3)
X
X
16
Heat valve
(1st stage heat)
Heat valve
(2nd stage heat)
Heat valve
(1st stage heat)
Heat valve
(2nd stage heat)
AO1
X
X
Cool valve PID
(3)
Cool valve PID
(3)
AO2
X
X
X
X
SW1
SW2
(1)
SW1.1, SW1.2 Fan speeds:
1 speed (Low):
2 speeds(Low and High):
3 speeds(Low, Medium, and High):
SW1.1 = ON, SW1.2 = OFF
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 – 2nd heating stage:
ON = Enable, OFF = Disable
(3)
SW1.5 – Chilled beam option:
ON = Enable chilled beam (fan will not run with 1st stage cooling)
(4)
SW2.3 – Dehumidification:
ON = Use dehumidifier
OFF = Use reheat for dehumidification
(5)
SW2.6 – Terminal 12 operation:
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (1/2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
See drawing in Wiring terminals and DIP switches (page 23) for DIP switch locations.
Fan VFS, PID valves, Hum., Dehum.: 0-10VDC. 0.5mA Not isolated
Control - Fan on/off, Heat elements, Cool/Heat valves, Economizer: 24VAC, 0.5A max.

Table of Contents

Related product manuals