EasyManua.ls Logo

Carrier ComfortVu Plus TBPL-H - Technician Settings P60 to P64

Carrier ComfortVu Plus TBPL-H
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
52
Technician Settings P60 to P64
P60
Fan turns ON when the Cool or Heat valve reaches the
“Proportional ON percent”
P61
Fan turns OFF when the Cool or Heat valve drops
below the “Proportional OFF percent”
P60 – Proportional ON percent (FC only)
Range: 0...30%
Default: 30%
P61 – Proportional OFF percent (FC only)
Range: 0...100%
Default: 100%
P63 – Time on-delay between cooling stages (AC only)
Range: 0…600 seconds
Default: 5 seconds
P64 – Time off-delay between cooling stages (AC only)
Range: 0…600 seconds
Default: 1 seconds

Table of Contents

Related product manuals