EasyManua.ls Logo

Carrier ComfortVu Plus TBPL-H - Technician Settings P11 to P15

Carrier ComfortVu Plus TBPL-H
71 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
42
Technician Settings P11 to P15
P11 – Window contact delay time
Range: 0…999 seconds.
Default: 600 seconds.
P12 – Door switch (terminals T1,0) polarity
“01” - Normally open
“00” - Normally closed
P13 – Door switch delay time
Range: 0…999 seconds.
Default: 180 seconds.
P14 – Enable/Disable Auto change over mode
“00” - Disable Auto change over mode
“01” - Enable Auto change over mode
P15 – Motion sensor logic (PIR)
“00” - Thermostat turns off when unoccupied and back on
when re-occupied.
“01” - Thermostat turns off when unoccupied and remains
off when re-occupied.
“02” - Thermostat uses economy setpoints when
occupied.
“03” - Unoccupancy Dehumidification logic
(only available with dehumidification configuration see DIP
switch settings)

Table of Contents

Related product manuals