EasyManua.ls Logo

Carrier GRAVINER Mk 7 - Page 104

Carrier GRAVINER Mk 7
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
March 2021 Page 93 of 143 59812-K007 Rev 17
Business Confidential
10. Using the following images on this page as a guide, apply the Graviner recommended glass
cleaning fluid to a foam bud and wipe carefully around the inside of the oil mist detection opening
in the Detector Head.
(Note: Do not use any electronic contact cleaners, isopropyl alcohols, flux removers, any harsh
chemical cleaners, etc., as these will affect the Detector performance.)
Figure 147 Sample Chamber Cleaning
11. Ensure that the glass ring around the side of the Detector Head and the small aperture shown
in the image above are thoroughly cleaned with the foam cleaning buds.
12. To ensure thorough cleaning Graviner recommend that steps 10 and 11 are repeated with
cleaning fluid applied to another foam bud.
13. Examine the Detector base body and sample tube and wipe clean where necessary.
14. Reassemble the Fan to the Detector Head using the Fan Retaining Plug.
CAUTION: Do not press the centre label of the fan, only handle the fan by the outer housing.
15. Reattach the Detector head to base and re-tighten the fixing screws. Attach the cable to the
Detector Head.
16. De-Isolate the Detector.

Table of Contents

Related product manuals