10. Using the following images on this page as a guide, apply the Graviner recommended glass 
cleaning fluid to a foam bud and wipe carefully around the inside of the oil mist detection opening 
in the Detector Head. 
(Note: Do not use any electronic contact cleaners, isopropyl alcohols, flux removers, any harsh 
chemical cleaners, etc., as these will affect the Detector performance.) 
 
   
Figure 147  Sample Chamber Cleaning 
11.  Ensure that the glass ring around the side of the Detector Head and the small aperture shown 
in the image above are thoroughly cleaned with the foam cleaning buds.  
12.  To ensure thorough cleaning Graviner recommend that steps 10 and 11 are repeated with 
cleaning fluid applied to another foam bud. 
13. Examine the Detector base body and sample tube and wipe clean where necessary. 
14. Reassemble the Fan to the Detector Head using the Fan Retaining Plug. 
CAUTION: Do not press the centre label of the fan, only handle the fan by the outer housing. 
15.  Reattach the Detector head to base and re-tighten the fixing screws. Attach the cable to the 
Detector Head.  
16. De-Isolate the Detector.