Slow Down Isolated  Indicates Yes if the Slowdown/Shutdown Relay is isolated. 
Watchdog Fault  Indicates Yes if a Control Unit software failure has caused the Control Unit 
to be automatically reset. 
Detector Fault  Indicates Yes if a fault has occurred on any detector on the engine. 
Memory Fault  Indicates Yes if a fault has been detected in the Control Unit memory 
3.5  TEST MENU 
Although  the Control  Unit  and  detectors  perform  continuous  automatic checks  a suit  of  tests  are 
provided to allow manual testing of the system functionality to be performed. 
To access the Test Menu, press the Test button 
 
Figure 87  Test Menu   User 
Slow Down Relay  This test is not available at User level 
Pre-Alarm Relay  -activates the relay. 
Fault Relay  -activates the relay. 
The Fault relay is normally activated and is deactivated to indicate a fault 
condition. 
Backup Alarm  The Control Unit checks the integrity  of the Backup  Alarm connection 
between the Control Unit and the detectors. At the end of the test the 
display with either show that the test has been passed or indicate the 
detector(s) that failed. 
Optics Test  Each detector performs an optics test to check for oil contamination within 
the detector sample chamber. At the end of the test the display will either 
show that the test has been passed or indicate the detector(s) that failed. 
Front Panel Test 
period and then switch on and off one at a time in sequence. This allows a 
visual check to be made of the membrane indications. 
3.6  EVENT LOG 
The Event Log enables the user to interrogate the past 1024 events and can be accessed via the menus 
below. The Event Log is a rolling buffer and when the events exceed 1024 then the oldest event is 
dropped off the Event Log. 
 
To access the Event Log from Figure 85