OFFSETS:
This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the
actual temperature/humidity values (defaults=0).
• Zone 1 Offset: -5 to +5 degrees.
• Outside Temp Offset: -5 to +5 degrees.
• Humidity Offset: -10 to +10 percent.
CYCLES PER HOUR:
• Maximum cycles per hour = 4 (default) or 6.
• Anticipator = 1 to 9 (default=3). This adjusts sensitivity
to temperature changes. 1 = most sensitive. 9 = least
sensitive.
• If space is over-conditioning, increase the anticipator
setting.
• If space is under-conditioning, decrease the anticipator
setting.
PROGRAMMING:
• ON (default)- allo``vs program schedule to be set by
user.
• OFF - system becomes non-programmable
• Periods Per Day = 2 or 4 (default=4)
• Programmable Fan On/Off (default=Off). If ON is
selected, fan can be set to Auto, Low, Med. or High.
SMART RECOVERY:
• On or Off, (default=On)
Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling
mode. Refer to operational information for more detail.
ENGLISH/METRIC DISPLAY
• °F or °C, (default = °F)
RESET FACTORY DEFAULTS:
Program Schedule:
• Yes/No to reset back to Energy Star default Time and
Temp schedules.
User Settings:
• Yes/No to reset the user settings in the Advanced Setup
to factory default settings.
Install Settings:
• Yes/No to reset install settings in Install/Service menus
to factory default settings.
Last 10 Faults:
• Yes/No to reset last 10 faults under Service Info menu.
SETUP -- FURNACE
Upon a first time start-up of the Infinity Control, the furnace DIP
switch settings will be copied to the furnace setup menu. Any
changes can then be made from the Infinity Control.
AIRFLOW:
• COMFORT (default)
• EFFICIENCY
Selects the airflow of the furnace when heating. EFFICIENCY
is the airflow used to meet specified ratings, COMFORT is a
decreased airflow used to increase the output air temperature and
provide increased comfort.
AC AIRFLOW
• COMFORT (default) - cooling airflow is varied
depending on humidity and temperature demands
settings. This selection enables the full dehumidify and
/
comfort capabilities of the system. When COMFORT
is not selected, the unit will not run reduced aiflo,,vs for
dehumidification.
• EFFICIENCY - fixed airflow used to achieve specified
ratings - no dehumidification airflow reduction. This
is nominally 350 CFM/ton, but will vary if a 2-stage
outdoor unit is used.
• MAXIMUM - 400 CFM/ton. Dehumidify features are
not active when set to maximum.
DEHUM AIRFLOW
• NORMAL (factory default) - When equipment is
running to dehumidify, the airflow is allowed to adjust
to a minimum to satisfy the dehumidification call.
• HIGH - Minimum airflo``vduring the dehumidify
mode is increased to reduce duct and register sweating.
LOW HEAT RISE
• ON
• OFF (default)
Set to ON if the system contains a bypass humidifier. The ON
setting ,,villincrease the furnace low heat airflov<
STAGING
• SYSTEM (default)
• LOW
• HIGH
• FURNACE
Controls the staging of the furnace. SYSTEM setting will allow
the Infinity Control to determine furnace staging. LOW will only
run the low stage of furnace heat. HIGH will only run the high
stage of furnace heat. FURNACE will allow the furnace
algorithm to control staging
OFF DELAY:
• 90 seconds
• 120 seconds (default)
• 150 seconds
• 180 seconds
Amount of time the blower will continue to run after heating has
shut off.
11