WIRING CONSIDERATIONS -- Ordinary thermostat wire is
recommended. Use 22 AWG or larger for normal wiring
applications. Continuous wire lengths over 100 ft. should use 20
AWG or larger.
NOTE:ABCD bus wiring only requires a four-wire connection;
however, it is good practice to run thermostat cable having more
than four wires in the event of a damaged or broken wire during
installation.
Each communicating device in the Infinity System has a four-pin
connector labeled ABCD. It is recommended that the following
color code be used when wiring each device:
A -- Green = Data A
B -- Yellow = Data B
C -- White = 24VAC (Com)
D -- Red = 24VAC (Hot)
It is not mandatory that the above color code be used. but each
ABCD connector in the system MUST be wired consistently.
MOUNTING INFINITY CONTROL -- There are two options
for mounting the Infinity Control to the wall. First, become
familiar with all plastic assembly pieces shown in Fig. 2 through
9. The User Interface will snap together with either the Recess
Mount or the Surface Mount backplate.
RECESS MOUNT -- This provides the thinnest mounting
configuration (See Fig. 3). The backplate containing the recessed
terminal block can be mounted directly to the wall by cutting a
hole 1 1/2" wide by 2 1/8" high. Mark location and cut hole in
wall.
NOTE: Always ensure the Infinity Control location is acceptable
before cutting any holes in wall.
SURFACE MOUNT -- This provides surface mounting
configuration, which allows use of a small hole in the wall. A
surface mount backplate is supplied (See Fig. 4). Attach
backplate as shown in Fig. 7, and the assembly will mount
directly to the wall requiring only a small hole in the wall
allowing a four wire connection to pass through.
NOTE: Once Infinity Control is secured to wall with the
backplate assembly (snapped together), care must be taken not to
bend or break the interlocking tabs when removing. Gently
remove Infinity Control by rocking up/down until interlocking
tabs release.
DECORATIVE BACKPLATE -- Supplied is a thin decorative
backplate (see Fig. 5), to hide any marks/screw holes left from the
previous thermostat. This decorative backplate (or beauty ring) can
be used in either the recess or surface mount installation by snapping
it onto back of recessed mount backplate or surface mount backplate
before securing to wall. See Fig. 8 and 9 for a larger decorative
backplate P/N SYSTXXOLBP01 (5.75" ,,vide X 6" tall), which can
be ordered separately.
Fig. 2 - Infinity " Control
A03185
888
%
Fig. 3 - Recessed Mount Backplate
A03186