PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
46
mark.  Quickly  apply  approved  cement  to  end  of  pipe  and  fitting
socket  (over  primer). Apply  cement  in  a  light,  uniform  coat  on
inside of socket to prevent buildup of excess cement. Apply second
coat. DO NOT CEMENT POLYPROPYLENE FITTINGS.
14. While cement is still wet,  twist pipe into socket with  1/4-in. turn.
Be sure pipe is fully inserted into fitting socket.
15. Wipe excess cement from joint. A continuous bead of cement will
be visible around perimeter of a properly made joint.
16. Handle pipe joints carefully until cement sets.
17. Horizontal  portions  of  the  venting  system  shall  be  supported  to
prevent  sagging.  Space  combustion  air  piping  and  vent  piping
hangers as shown in Table 17. Support pipes using perforated metal
hanging strap or commercially available hangers or straps designed
to support plastic pipe.
Table 17 – Hanger Spacing
18. Slope  the  vent  and  combustion  air  piping  downward  towards
furnace. A  minimum  slope  of  at  least  1/4-in.  (6  mm)  per  linear
ft.(1-in (25 mm) per 4 ft.(1.2 M)) with no sags between hangers is
required. See Caution Box below.
19. Use  appropriate  methods  to  seal  openings  where  combustion  air
pipe and vent pipe pass through roof or sidewall.
Installing the Vent Termination
Roof Terminations
A roof termination of any type will require a 4-in. (102 mm) flashing for
a  2  in.  (50  mm  ND)  concentric  vent  kit,  KGAVT0701CVT or  a  5-in.
diameter (127 mm) flashing for a 3-in. (80 mm ND) concentric vent kit,
KGAVT0801CVT. For two-pipe or single pipe vent systems, a flashing
for each pipe of the required diameter will be necessary. 
It is recommended that the flashing be installed by a roofer or competent
professional prior to installing the concentric vent. The terminations can
be installed on a flat or pitched roof.
Concentric Vent
Single or multiple concentric vent must be installed as shown in Fig. 39.
Maintain the required separation distance between vents or pairs of vents
as shown in Fig. 39 and all clearance shown in Fig. 42.
NOTE:    Follow  the  instructions  of  the  vent  terminal  manufacturer.
These instructions are provided as a reference, only.
Cut one 4-in. (102 mm) diameter hole for 2-in. (50 mm ND) kit, or one
5-in. (127 mm) diameter hole for 3-in. (80 mm  ND) kit in  the desired
location. 
Loosely  assemble  concentric  vent/combustion  air  termination
components together using instructions in kit.
Slide assembled kit with rain shield REMOVED through hole in wall or
roof flashing.
NOTE:  Do not allow insulation or other materials to accumulate inside
of pipe assembly when installing it through hole.
Disassemble  loose  pipe  fittings.  Clean  and  cement  using  same
procedures  as  used  for  system  piping.  DO  NOT  CEMENT
POLYPROPYLENE FITTINGS.
Two-Pipe and Single-Pipe Terminations
Single  and  two  pipe  vent  must  be  installed  as  shown  in  Fig. 39  and
Fig. 40. Maintain the required separation distance between vents or pairs
of  vents  as  shown  in  Fig. 39  and  Fig. 40  and  all  clearance  shown  in
Fig. 42 and Fig. 43.
Cut  the  required  number  of  holes  in  the  roof or  sidewall  for vent  and
(when  used)  combustion  air  pipes.  Sidewall  holes  for  two-pipe  vent
terminations should be  side-by-side, allowing  space between the  pipes
for the elbows to fit on the pipes.
Holes in the roof for direct-vent two-pipe terminations should be spaced
no more than 18 in. (457 mm) apart to help avoid vent gas recirculation
into combustion air intake.
Termination  elbows  will  be  installed  after  the  vent  and  (if  used)
combustion air pipe is installed.
Sidewall Terminations
Concentric Vent
NOTE:    Follow  the  instructions  of  the  vent  terminal  manufacturer.
These instructions are provided as a reference only.
Determine an appropriate location for termination kit using the
guidelines provided in section “Locating The Vent Termination” in
this instruction.
1. Cut one 4-in. diameter hole for 2-in. kit, or one 5-in. diameter hole
for 3-in. kit.
2. Loosely  assemble  concentric  vent/combustion  air  termination
components together using instructions in kit.
3. Slide assembled kit with rain shield REMOVED through hole.
NOTE:  Do not allow insulation or other materials to accumulate inside
of pipe assembly when installing it through hole.
Diameter
Material
PVC Sch 
40
SDR 21 & 
26
ABS CPVC
Polypro-
pylene
1 1/2-in. 3-ft. 2 1/2-ft. 3-ft. 3-ft. 3.25-ft.
38-mm 914-mm 762-mm 914-mm 914-mm 1000 mm
2-in. 3-ft. 3-ft. 3-ft. 3-ft. 3.25-ft.
51-mm 914-mm 914-mm 914-mm 914-mm 1000 mm
2 1/2-in. 3 1/2-ft. 3-ft. 3 1/2-ft. 3 1/2-ft. 3.25-ft.
64-mm 1067-mm 914-mm 1067-mm 1067-mm 1000 mm
3-in. 3 1/2-ft. 3-ft. 3 1/2-ft. 3 1/2-ft. 3.25-ft.
76-mm 1067-mm 914-mm 1067-mm 1067-mm 1000 mm
4-in. 4-ft. 3 1/2-ft. 4-ft. 4-ft. 3.25-ft.
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure  to  follow  this  caution  may  result  in  nuisance  short  cycling,
frozen vent termination, and/or no heat.
Slope the vent and combustion air piping downward towards furnace a
minimum of 1/4-in. (6 mm) per linear ft. of pipe.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
DO  NOT  use  cement to join  polypropylene  venting systems. Follow
the  polypropylene  venting  system  manufacturer’s  instructions  for
installing polypropylene venting systems.
NOTICE
!
FOR POLYPROPYLENE VENTING SYSTEMS
When using polypropylene venting systems, all venting materials used,
including the vent terminations, must be from the same manufacturer.
NOTICE
!
RECOMMENDED SUPPORT FOR VENT TERMINATIONS
It is recommended that rooftop vent terminations in excess of 36 inches
(1  M)  in  vertical  length  be  supported  by  EITHER  the  Direct  Vent
Termination  Kit  shown  in  Table 12  or  by  field-supplied  brackets  or
supports fastened to the structure.