T-362 4–56
4.6.7 DataCORDER Communications
Hardware
DataCORDER uploads or downloads on a unit with an ML3 controller can be accomplished with one of the
following methods:
Using the programming slot in the controller with the choice of hardware options:
PCMCIA sRAM Card. (This is obsolete but still supported)
USB Adapter with USB. (One USB for upload, one USB for download)
MUA Adapter with USB (PN 07-00571-00). (The adapter stays in the controller)
MST Service Tool with USB (PN 07-00572-00). (The service tool is temporary in the controller)
Connecting a laptop to the Interrogator port.
Refer to Controller Programming procedures in the Service chapter for upload / download procedures.
Software
Downloaded and real-time data from the DataCORDER can be viewed in the original DataLINE software or the
ContainerLINK™ app.
DataLINE is the original windows program that allows
interrogation, configuration variable assignment, screen
view of the data, hard copy report generation, cold treatment probe calibration and file management.
DataLINE 3.12 is most likely the last release of DataLINE. See DataLINE operations manual 62-10629 for
detailed procedures.
ContainerLINK is an app for smart phones, tablets and Windows computers. The functionality of the original
DataLINE software is now integrated into ContainerLINK.
.
P6-7 Digital Unloader Valve Test Pass / Fail / Skip
P6-9 Liquid Injection Valve Test (If equipped) Pass / Fail / Skip
P6-10 Electronic Expansion Valve Test Pass / Fail / Skip
P7-0 High Pressure Switch Closed Pass / Fail / Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
P7-1 High Pressure Switch Open Pass / Fail / Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
P8-0 Perishable Mode Heat Test Pass / Fail / Skip Result, STS, time it takes to heat to 16°C
(60°F)
P8-1 Perishable Mode Pulldown Test Pass / Fail / Skip Result, STS, time it takes to pull down to
0°C (32°F)
P8-2 Perishable Mode Maintain Test Pass / Fail / Skip Result, Averaged DataCORDER supply
temperature (SRS) over last recording interval.
P9-0 Defrost Test Pass / Fail / Skip Result, DTS reading at end of test, line
voltage, line frequency, time in defrost.
P10-0 Frozen Mode Heat Test Pass / Fail / Skip Result, STS, time unit is in heat.
P10-1 Frozen Mode Pulldown Test Pass / Fail / Skip Result, STS, time to pull down unit to -
17.8°C (0°F).
P10-2 Frozen Mode Maintain Test Pass / Fail / Skip Result, Averaged DataCORDER return
temperature (RRS) over last recording interval.
Table 4–11 DataCORDER Pre-Trip Result Records (Continued)
Test Title Data