6.7 - Control point
The control point represents the water temperature that the unit
must produce. The required capacity can be decreased depending
on the unit load operating conditions.
Control point = Active setpoint + Reset
The control point is calculated based on the active setpoint and
the reset calculation. The forced value can be used instead of any
other setpoint calculation only when the unit is in the Network
operating type.
6.7.1 - Active setpoint
Two setpoints can be selected. Depending on the current operation
type, the active setpoint can be selected manually via the Main
menu (GENUNIT – General Parameters), with the volt-free user
contacts, with network commands (CCN or BACnet) or automatically
with the setpoint time schedule (schedule 2).
The following tables summarise possible selections depending on
the control operating type (Local, Remote or Network) and the
following parameters:
■ Heating or Cooling operating mode [hc_sel]: Heat/Cool
select (GENUNIT menu).
■ Setpoint selection [sp_sel]: Setpoint select permits selection
of the active setpoint if the unit is in the Local operating type
(GENUNIT menu).
■ Setpoint switch status [SETP_SW]: Remote Setpoint Switch
(INPUTS menu).
■ Schedule 2 status [SP_OCC]: Schedule for setpoint selection.
LOCAL OPERATING TYPE
Parameter status
Active setpoint
Heating/cooling
Setpoint
selection
Ice storage
conguration
Ice done contact Setpoint switch
Schedule 2
status
cooling sp-1 - * * - cooling setpoint 1 (csp1)
cooling sp-2 - * * - cooling setpoint 2 (csp2)
cooling * enabled open closed - cooling ice setpoint (Ice_sp)
cooling * enabled closed closed - cooling setpoint 2 (csp2)
cooling * - * open - cooling setpoint 1 (csp1)
cooling auto - * * occupied cooling setpoint 1 (csp1)
cooling auto - * * unoccupied cooling setpoint 2 (csp2)
cooling auto enabled open * unoccupied cooling ice setpoint (Ice_sp)
heating sp-1 - * * - heating setpoint 1 (hsp1)
heating sp-2 - * * - heating setpoint 2 (hsp2)
heating auto - * * occupied heating setpoint 1 (hsp1)
heating auto - * * unoccupied heating setpoint 2 (hsp2)
*Any conguration, (-) default conguration.
REMOTE OPERATING TYPE
Parameter status
Active setpoint
Heating/cooling
Setpoint
selection
Ice storage
conguration
Ice done contact Setpoint switch
Schedule 2
status
cooling * enabled open closed - cooling ice setpoint (Ice_sp)
cooling * - * open - cooling setpoint 1 (csp1)
cooling - - * open - cooling setpoint 1 (csp1)
cooling - - * closed - cooling setpoint 2 (csp2)
heating - - * open - heating setpoint 1 (hsp1)
heating - - * closed - heating setpoint 2 (hsp2)
*Any conguration, (-) default conguration.
NETWORK OPERATING TYPE
Parameter status
Active setpoint
Heating/cooling
Setpoint
selection
Ice storage
conguration
Ice done contact Setpoint switch
Schedule 2
status
cooling - - * * occupied cooling setpoint 1 (csp1)
cooling - - * * unoccupied cooling setpoint 2 (csp2)
heating - - * * occupied heating setpoint 1 (hsp1)
heating - - * * unoccupied heating setpoint 2 (hsp2)
*Any conguration, (-) default conguration.
IMPORTANT: Ice storage conguration [ice_cnfg] and ice
done contact [ice_done] apply only to units with EMM.
6 - STANDARD CONTROL OPERATIONS AND OPTIONS
40