EasyManua.ls Logo

Carrier SmartView - Capacity Control; Night Mode; Coil Pressure Control; Energy Management Module

Carrier SmartView
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.9 - Capacity control
The control adjusts the capacity to keep the water exchanger
temperature at its setpoint. Compressors are started and stopped
in a sequence designed to equalise the number of start-ups (value
weighted by their operating time).
6.9.1 - Circuit loading sequence
This function determines in which order the circuit capacity is
changed. Compressor loading is managed by starting/stopping the
compressors. Two types of sequencing, i.e. balanced and staged
loading sequence, are available and can be congured by the user 
via the user interface (GEN_CONF – General Conguration).
Balanced loading sequence: The control maintains equal
capacity between all circuits as the machine loads and unloads.
Balanced loading sequence is the default sequence employed by
the control.
Staged loading sequence: The control loads the lead circuit
completely before the lag circuits are started. When the load is
decreasing, the lag circuit is unloaded first. Staged loading
sequence is active when one of the circuits is shut down due to
its failure; the circuit is in capacity override mode; or the remaining
circuits are shut down or fully charged.
To set the circuit loading sequence
1. Navigate to the Conguration menu.
2. Select General Conguration (GEN_CONF).
3. Set Staged loading sequence [seq_typ].
Staged loading sequence [seq_typ]
No/Yes No
6.9.2 - Capacity for multi-circuit unit
The circuit lead/lag function determines the lead and lag circuit of
the unit. This function controls the start/stop sequence of two
refrigeration circuits called circuit A and circuit B.
The circuit authorised to start rst is the lead circuit. Lead circuit 
is used rst for capacity increases and at the  same time should 
be decreased rst when decreasing capacity. The lead/lag circuits 
can be selected manually or automatically (Cir Priority Sequence,
GEN_CONF – General Conguration).
Manual lead/lag circuit determination: Circuit A or circuit B
selected as the lead circuit. The selected circuit takes priority
over another circuit.
Automatic lead/lag circuit determination: The control system
determines the lead circuit to equalise the operating time of each
circuit (value weighted by the number of start-ups of each circuit).
As a result, the circuit with the lowest number of operating hours
always starts rst.
To set circuit priority
1. Navigate to the Conguration menu.
2. Select General Conguration (GEN_CONF).
3. Set Cir Priority Sequence [prio_cir].
Cir Priority Sequence [prio_cir]
0 Auto
1 Circuit A priority
2 Circuit B priority
6.10 - Night mode
Night  mode  allows  users  to  congure  the  unit  to  operate  with 
specic  parameters  in  a  specic  time  period.  During  the  night 
period, the unit capacity is limited. The number of operating fans
is reduced (in cooling mode only).
The night period is dened by a start time and an end time that 
are the same for each day of the week. The Night mode settings
or the maximum capacity value can be configured via the
Conguration menu (GEN_CONF – General Conguration). Only 
logged-in users can modify the night mode settings.
To set the night mode
1. Navigate to the Conguration menu (logged-in users only). 
2. Select General Conguration (GEN_CONF).
2. Set parameters corresponding to the night mode.
Night Mode Start Hour [nh_start]
00:00 to 24:00
Night Mode End Hour [nh_end]
00:00 to 24:00
Night Capacity Limit [nh_limit]
0 to 100% 100%
6.11 - Coil pressure control
The coil pressure of each circuit is managed by four fans maximum.
30RBM/RQM units are tted with xed speed fans and 30RBP/
RQP units are tted with variable speed fans providing higher part 
load efciency and reduced acoustic levels. 
In cooling mode, the condensing pressure is controlled
independently in each circuit based on the saturated condensing
temperature. The control permanently adjusts its setpoint to
guarantee optimal performance and ensure anti-short-cycle
protection of the fans.
In heating mode, the evaporating pressure is controlled independently
on each circuit based on the saturated suction temperature.
The control permanently adjusts its setpoint to guarantee optimal
performance, delay and limit frost accumulation on coils.
6.12 - Energy management module
The optional Energy Management Module is used to control the
level of energy consumption, providing users with information such
as current unit status, compressors operating status, etc.
For more information about connections associated with the
energy management module, see section 3.3.
6 - STANDARD CONTROL OPERATIONS AND OPTIONS
42

Table of Contents

Related product manuals