5.6 - System menu
Home Main MenuPrevious screen System Menu
User Login
Start / Stop Alarms Menu
System menu
CPU Load EOL Resistor Network
Date/Time Conguration Language & Unit System Brightness
Software Info Hardware Info
Basic access (no password)
User password required
Legend:
5 - SMARTVIEW CONTROL: MENU STRUCTURE
The System menu allows the user to verify software, hardware,
or network information and change some display settings, including
language, date/time, or brigtness.
To access the System menu, press the System menu button
located in the upper-right part of the Home screen.
CAUTION: Since specic units may not include additional
features, some tables may contain parameters that cannot
be congured for a given unit.
CPU Load Menu – CPULOAD
Status Default Unit Displayed text* Description
0 to 100 - % CPU load CPU utilization
0 to 100 - % RAM Memory utilization RAM usage
0 to 100 - % FLASH Memory utilization Flash memory usage
*Depends on the selected language (English by default).
EOL Resistor Menu – EOLRES
Status Default Displayed text* Description
disable/enable disable End of Line Res. J6(LEN) End of line resistor J6 (LEN bus)
disable/enable disable End of Line Res. J7(CCN) End of line resistor J7 (CCN bus)
disable/enable disable End of Line Resistor J8 End of line resistor J8
disable/enable disable End of Line Resistor J10 End of line resistor J10 (Modbus)