ModbusTCP/IP Cong. – MODBUSIP
Name Status Default Unit Displayed text* Description
modip_en no/yes no - TCP/IP Server Enable TCP/IP Server Enable
ser_UID 1 to 247 1 - Server UID Server UID
port_nbr 0 to 65535 502 - IP Port Number IP Port Number
metric no/yes yes - Metric Unit Metric Unit
swap_b 0 to 1 0 - Swap Bytes Swap Bytes
0 = Big Endian 0 = Big Endian
1 = Little Endian 1 = Little Endian
real_typ 0 to 1 1 - Real Type Management Real Type Management
0 = Float X10 0 = Float X10
1 = IEE 754 1 = IEE 754
reg32bit 0 to 1 1 - Enable 32 bits registers Enable 32 bits registers
0 = IR/HR in 16 bit mode 0 = IR/HR in 16 bit mode
1 = IR/HR in 32 bit mode 1 = IR/HR in 32 bit mode
conifnam 0 to 1 0 - IP port interface name IP port interface name
0 = J5/J15 0 = J5/J15
1 = J16 1 = J16
timeout 60 to 600 120 sec Com. timeout (s) Com. timeout (s)
idle 0 to 30 10 sec Keepalive idle delay(s) Keepalive idle delay(s)
intrvl 0 to 2 1 sec Keepalive interval(s) Keepalive interval(s)
probes 0 to 10 10 - Keepalive probes nb Keepalive probes nb
*Depends on the selected language (English by default).
NOTE: If you need to add an option, please contact your local
carrier Service provider.
BACnet Conguration – BACNET
Name Status Default Unit Displayed text* Description
bacena disable/enable disable - BACnet Enable BACnet Enable
bacunit no/yes yes - Metric Unit Metric Unit
network 1 to 9999 1600 - Network Network
udpport 40000 to 47823 47808 - UPD (Displayed Text and Description) UPD (Displayed Text and Description)
ident 0 to 9999999 1600001 - Identier Identier
auid_opt disable/enable disable - Device Id Manual Device Id Manual
balmena disable/enable enable - Alarm reporting Alarm reporting
mng_occ no/yes no - BACnet Manage Occupancy BACnet Manage Occupancy
conifnam 0 to1 0 - IP port Interface name IP port Interface name
0 = J5/J15 0 = J5/J15
1 = J16 1 = J16
*Depends on the selected language (English by default).
NOTE: If you need to add an option, please contact your local
carrier Service provider.
5 - SMARTVIEW CONTROL: MENU STRUCTURE
28