6.23 - Software Activation Key(s)
30RB/RQ units with SmartView offer some additional options which
require Software Activation Keys:
■ Cooler uid type:
- Medium brine (option 5)
- Low brine (option 6)
■ BACnet communication (option 149)
■ Modbus communication (option 149B)
These software-protected options can be factory-installed or
installed on-site by the service technician or the customer.
Each option requires an individual software activation key.
To obtain the Software Activation Key, please contact your local
Carrier Service representative.
6.23.1 - Software options
The list of available software activation keys can be veried via
the Main menu.
To verify available software options
1. Go to the Main menu.
2. Select Software Options (OPT_STA).
The menu can be accessed when logged in at user access level.
• If the status of the option is set to “yes”, it means that the
Software Activation Key for this option is installed.
IMPORTANT: In case the controller is replaced, the Software
Activation Key must be installed again. See also section 6.23.2.
6.23.2 - Replacement mode
To enable the use of software options until the Software Activation
Key(s) is(are) installed, the Replacement mode will be activated.
■ Software options will be unlocked for a limited period of time
(7 days since the rst start of the compressor).
■ Only options that have been installed on the unit before will be
active in the Replacement mode. Option status can be veried
via the Main menu (OPT_STA – Software Options).
■ Alarm 10122 will be triggered. If the Software Activation Key is not
provided within 7 days since the rst compressor start, the alarm
will be reset automatically and software options will be blocked.
■ The Replacement mode ends when the Software Activation
Key is installed or the period of 7 days elapsed (7 days since
the rst compressor start).
6.23.3 - Software key installation
To install the Software Activation Key via SmartView
1. Go to the Main menu.
2. Navigate to the Conguration menu (logged-in users only).
3. Select Add Options (ADD_OPT).
• When installing the Software Activation Key, please make
sure that the unit is stopped.
B
C
Legend:
1. Controller MAC address
2. Software Activation Key
4. Enter the Software Activation Key.
• If the Software Key ends with two equality signs (==), then
these signs can be omitted. The Key will be accepted.
• The Software Activation Key is case-sensitive.
5. Once the Software Activation Key is provided in the Keyboard
screen, press OK.
6. Once the Software Activation Key is validated, the following
message will be displayed: “Software Activation Key Added”.
7. The parameter connected with the activated functionality is
set automatically and the control system will also be rebooted
automatically.
• If the Software Activation Key is incorrect, the following
message will be displayed: “Software Activation Key is Invalid”.
• If the Software Activation Key has been added before,
the following message will be displayed: “Key Already Set”.
6 - STANDARD CONTROL OPERATIONS AND OPTIONS
45